Command 272 (0x0110) – Display target visualisation
20593
This command enables switching between the menu page of the GUI and the target visualisation as
well as enables/disables the use of the key combination [
] + [
].
>
Command request channel (fieldbus master >>> device)
20594
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
UID
2
command number
3
TargetVisu
4
Hotkey
5...120
The area is completely ignored.
It does not matter whether the data area exists or what data is contained.
Legend:
TargetVisu
Content of the device
display
1 Word 0x0000 = display GUI
0x0001 = display target visualisation
Hotkey
Key combination for
switching from target
visualisation to the menu
page of the GUI
1 Word 0x0000 = key combination enabled
0x0001 = key combination disabled
>
Command reply channel (device >>> fieldbus master)
20595
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
2
reflected command number
3
reserved
Command status
(
→ page
4
command error code
>
Possible command error codes
20596
Error Code
[hex]
Error
Meaning
0x00
no error
0x01
Target visualisation cannot be displayed because CODESYS PLC is not active
Error code appears if command status = FAILED