Parameters: Independent mode
11058
Parameter
Description
Value range
Analogue channels per input slave
Number of analogue channels
per input slave
4 channels* =
4 channels
(variable slave assignment)
2 channels =
2 channels
(fixed slave assignment)
1 channel =
1 channel
(fixed slave assignment)
1 channel per
A/B slave =
1 channel per A/B slave
(fixed slave assignment)
Analogue channels per output slave
Number of analogue channels
per output slave
4 channels* =
4 channels
(variable slave assignment)
2 channels =
2 channels
(fixed slave assignment)
1 channel =
1 channel
(fixed slave assignment)
1 channel per
A/B slave =
1 channel per A/B slave
(fixed slave assignment)
Fail-safe state
Behaviour of the slave outputs if
an interrupted fieldbus
connection is detected
Reset
outputs* =
All AS-i outputs are switched off in
case of an interrupted EtherNet/IP
connection (value = 0).
Hold outputs =
The outputs are held in the last valid
state that existed before the
interrupted connection was
detected.
Change byte order
Byte order in a word
Setting applies to all data of
object class 4, instances 100
and 150
Disabled* =
Byte order in word remains
unchanged.
Enabled =
Byte order in word is inverted.
* ... Default setting