Electronic Preset Counter E89005
8
3.3 Outputs
2 relay outputs with potential-free contacts
(→ 11.6 Outputs)
�
3.3.1 Active Outputs
An active output will be shown on the display�
6 Outputs
6.1 Output
1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2 Output
2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3 Active
Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1 Entering
the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
7.3 Entering
a sub-menu
The sub-menu is opened with the
Prog/Mode key and the first
menu item is displayed.
7.4
Selecting the menu items
The Prog/Mode key is used to
select a menu item within the
sub-menu
7.5
Setting the menu items
The T2 key is used to select the
individual settings for the menu
items
When setting count values, each
decade has a key assigned to it.
Each time the key is pressed,
the value increments by one
7.6 Accepting
the setting
Pressing the Prog/Mode key
causes the current setting to be
accepted. Programming then
switches to the next menu item.
7.7
Ending the programming
During programming, it is possible to exit the
programming at each menu item by pressing the
reset key.
Press the Reset key
The security prompt
appears in the display
Pressing the Prog/Mode key
acknowledges this prompt and
causes the programming menu
to start again from the beginning.
The previously-programmed
values are preserved. These can
now be changed or checked
again.
Pressing the decade key T2
selects the termination of the
programming
The security prompt
appears in the display
Seite 6
/
6 Outputs
6.1 Output
1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2 Output
2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3 Active
Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1 Entering
the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
7.3 Entering
a sub-menu
The sub-menu is opened with the
Prog/Mode key and the first
menu item is displayed.
7.4
Selecting the menu items
The Prog/Mode key is used to
select a menu item within the
sub-menu
7.5
Setting the menu items
The T2 key is used to select the
individual settings for the menu
items
When setting count values, each
decade has a key assigned to it.
Each time the key is pressed,
the value increments by one
7.6 Accepting
the setting
Pressing the Prog/Mode key
causes the current setting to be
accepted. Programming then
switches to the next menu item.
7.7
Ending the programming
During programming, it is possible to exit the
programming at each menu item by pressing the
reset key.
Press the Reset key
The security prompt
appears in the display
Pressing the Prog/Mode key
acknowledges this prompt and
causes the programming menu
to start again from the beginning.
The previously-programmed
values are preserved. These can
now be changed or checked
again.
Pressing the decade key T2
selects the termination of the
programming
The security prompt
appears in the display
Seite 6
For safety switching the relay outputs can be inverted, i�e� the relay will be
deenergized when the presets are reached� To do this, the parameters Pr�OUT1
and Pr�OUT2 must be set to
6 Outputs
6.1 Output
1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2 Output
2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3 Active
Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1 Entering
the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
7.3 Entering
a sub-menu
The sub-menu is opened with the
Prog/Mode key and the first
menu item is displayed.
7.4
Selecting the menu items
The Prog/Mode key is used to
select a menu item within the
sub-menu
7.5
Setting the menu items
The T2 key is used to select the
individual settings for the menu
items
When setting count values, each
decade has a key assigned to it.
Each time the key is pressed,
the value increments by one
7.6 Accepting
the setting
Pressing the Prog/Mode key
causes the current setting to be
accepted. Programming then
switches to the next menu item.
7.7
Ending the programming
During programming, it is possible to exit the
programming at each menu item by pressing the
reset key.
Press the Reset key
The security prompt
appears in the display
Pressing the Prog/Mode key
acknowledges this prompt and
causes the programming menu
to start again from the beginning.
The previously-programmed
values are preserved. These can
now be changed or checked
again.
Pressing the decade key T2
selects the termination of the
programming
The security prompt
appears in the display
Seite 6
(for permanent signal) or
6 Outputs
6.1 Output
1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2 Output
2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3 Active
Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1 Entering
the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
7.3 Entering
a sub-menu
The sub-menu is opened with the
Prog/Mode key and the first
menu item is displayed.
7.4
Selecting the menu items
The Prog/Mode key is used to
select a menu item within the
sub-menu
7.5
Setting the menu items
The T2 key is used to select the
individual settings for the menu
items
When setting count values, each
decade has a key assigned to it.
Each time the key is pressed,
the value increments by one
7.6 Accepting
the setting
Pressing the Prog/Mode key
causes the current setting to be
accepted. Programming then
switches to the next menu item.
7.7
Ending the programming
During programming, it is possible to exit the
programming at each menu item by pressing the
reset key.
Press the Reset key
The security prompt
appears in the display
Pressing the Prog/Mode key
acknowledges this prompt and
causes the programming menu
to start again from the beginning.
The previously-programmed
values are preserved. These can
now be changed or checked
again.
Pressing the decade key T2
selects the termination of the
programming
The security prompt
appears in the display
Seite 6
or
6 Outputs
6.1 Output
1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2 Output
2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3 Active
Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1 Entering
the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
7.3 Entering
a sub-menu
The sub-menu is opened with the
Prog/Mode key and the first
menu item is displayed.
7.4
Selecting the menu items
The Prog/Mode key is used to
select a menu item within the
sub-menu
7.5
Setting the menu items
The T2 key is used to select the
individual settings for the menu
items
When setting count values, each
decade has a key assigned to it.
Each time the key is pressed,
the value increments by one
7.6 Accepting
the setting
Pressing the Prog/Mode key
causes the current setting to be
accepted. Programming then
switches to the next menu item.
7.7
Ending the programming
During programming, it is possible to exit the
programming at each menu item by pressing the
reset key.
Press the Reset key
The security prompt
appears in the display
Pressing the Prog/Mode key
acknowledges this prompt and
causes the programming menu
to start again from the beginning.
The previously-programmed
values are preserved. These can
now be changed or checked
again.
Pressing the decade key T2
selects the termination of the
programming
The security prompt
appears in the display
Seite 6
(for timed
signal)� See
(→ 2 Safety instructions)
�
4 Mounting
CAUTION
Mount the device away from heat sources and avoid direct contact with corrosive
liquids, hot steam or similar�
►
Remove mounting clip from the device�
►
Insert the device from the front into the panel cut-out, ensuring the front-panel
gasket is correctly seated�
►
Slide the fixing clip from the rear onto the housing, until the spring clamps are
under tension and the upper and lower latching lugs have snapped into place�