background image

Electronic Preset Counter E89005

36

Display

Description

Submenu

Value

StArt

Start delay

00.0

Factory setting

00.0...99.9

Programmable from 00�0 to 99�9 s�
At the start of a measurement the measurement results within this time-

period are ignored�

WAit0

Waiting time

00.1

Factory setting

00.1...99.0

Programmable from 00�1 to 99�9 s�
This value specifies how much time should elapse, after the last valid edge, 

before zero is to be displayed�

CoLor

Display colour (not supported)

rEd

Upper line red� 

Lower line red�

rEdGrn

Upper line red 

Lower line green

factory settings are highlighted in grey

8.6.3  Preset 1

Submenues for preset 1�

Display

Description

Submenu

Value

PrES 1

Submenu for turning preset 1 ON/OFF

on

Preset 1 ON

off

Preset 1 OFF and no function

Pr.Out 1

Preset output 1

   

    

       

Tracking preset mode 

When preset 2 is changed then 

preset 1 automatically tracks it.  

Reset to zero 
 

Preset 1 relative to preset 2 (see 

also section 17. Output 

operations) 
Tracking Preset mode with 

automatic reset 

When preset 2 is changed then 

preset 1 automatically tracks it.  

Reset to zero. 

Automatic reset to zero when 

main counter = preset value 2. 

Preset 1 relative to Preset 2  
(see also section 17. Output 

operations) 

7.8.6.3 

Submenu for configuration 

 

Submenu for matching the time 

ranges and display 

 
Unit of time 
Unit of time: seconds 

Decimal point setting determines 

the resolution 

 
Unit of time: minutes 

Decimal point setting determines 

the resolution 

 
Unit of time: hours 

Decimal point setting determines 

the resolution 

 
Unit of time:  Hrs. Min. Sec. 

 
 

Decimal point setting (Resolution) 

Decimal place 

(determines the resolution) 

 

no decimal place 

0.0   

1 decimal place 

0.00   

2 decimal places 

0.000  

3 decimal places  

Set value 

Set value can be programmed 

from  000000 to 999999 

A previously programmed 

decimal point will be displayed 

 

 

 

Display colour (for 6.92x.x1x3.xx0] 

Display colour 

upper line   

red 

lower line   

red 

 

 

 

Display colour 

upper line   

red 

lower line   

green 

 

7.8.6.4  Submenu for reset mode 

Setting the reset mode 
 
 
Manual reset (with red key) and 

electrical reset (reset input) 
 
No reset possible (red key and 

reset input inhibited) 

 

 
Only electrical reset possible 

(reset input) 

 

 

Only manual reset possible (red 

key) 
 

 

 

7.8.6.5  Submenu for Preset 1 

Submenu for turning preset 1 

ON/OFF  

 

 
Preset 1 ON 
 

 

 
Preset 1 OFF and no function 
 

 

 
ADD mode output operations: 

permanent signal at Output 1, 

becomes active when count > 

Preset 1  

SUB mode output operations: 

permanent signal at Output 1, 

becomes active when count < 

Preset 1  

 

ADD mode output operations: 

permanent signal at Output 1, 

becomes passive when count > 

Preset 1 

Seite 14

ADD mode output operations: 

permanent signal at Output 1, becomes active when count ≥ Preset 1

SUB mode output operations: 

permanent signal at Output 1, becomes active when count ≤ Preset 1

   

    

       

Tracking preset mode 

When preset 2 is changed then 

preset 1 automatically tracks it.  

Reset to zero 
 

Preset 1 relative to preset 2 (see 

also section 17. Output 

operations) 
Tracking Preset mode with 

automatic reset 

When preset 2 is changed then 

preset 1 automatically tracks it.  

Reset to zero. 

Automatic reset to zero when 

main counter = preset value 2. 

Preset 1 relative to Preset 2  
(see also section 17. Output 

operations) 

7.8.6.3 

Submenu for configuration 

 

Submenu for matching the time 

ranges and display 

 
Unit of time 
Unit of time: seconds 

Decimal point setting determines 

the resolution 

 
Unit of time: minutes 

Decimal point setting determines 

the resolution 

 
Unit of time: hours 

Decimal point setting determines 

the resolution 

 
Unit of time:  Hrs. Min. Sec. 

 
 

Decimal point setting (Resolution) 

Decimal place 

(determines the resolution) 

 

no decimal place 

0.0   

1 decimal place 

0.00   

2 decimal places 

0.000  

3 decimal places  

Set value 

Set value can be programmed 

from  000000 to 999999 

A previously programmed 

decimal point will be displayed 

 

 

 

Display colour (for 6.92x.x1x3.xx0] 

Display colour 

upper line   

red 

lower line   

red 

 

 

 

Display colour 

upper line   

red 

lower line   

green 

 

7.8.6.4  Submenu for reset mode 

Setting the reset mode 
 
 
Manual reset (with red key) and 

electrical reset (reset input) 
 
No reset possible (red key and 

reset input inhibited) 

 

 
Only electrical reset possible 

(reset input) 

 

 

Only manual reset possible (red 

key) 
 

 

 

7.8.6.5  Submenu for Preset 1 

Submenu for turning preset 1 

ON/OFF  

 

 
Preset 1 ON 
 

 

 
Preset 1 OFF and no function 
 

 

 
ADD mode output operations: 

permanent signal at Output 1, 

becomes active when count > 

Preset 1  

SUB mode output operations: 

permanent signal at Output 1, 

becomes active when count < 

Preset 1  

 

ADD mode output operations: 

permanent signal at Output 1, 

becomes passive when count > 

Preset 1 

Seite 14

ADD mode output operations: 

permanent signal at Output 1, becomes passive when count ≥ Preset 1

SUB mode output operations: 

permanent signal at Output 1, becomes passive when count ≤ Preset 1

   

    

       

SUB mode output operations: 

permanent signal at Output 1, 

becomes passive when count < 

Preset 1 
ADD mode output operations: 

timed signal at  Output 1, 

becomes active when count > 

Preset 1. (Activation only in 

positive direction) 

SUB mode output operations: 

timed output at Output 1, 

becomes active when count < 

Preset 1 (Activation only in 

negative direction) 
ADD mode output operations: 

timed signal at Output 1, 

becomes passive when count > 

Preset 1. (Deactivation only in 

positive direction) 

SUB mode output operations: 

timed output at Output 1, 

becomes passive when count < 

Preset 1. (Deactivation only in 

negative direction). 
ADD mode output operations: 

timed signal at Output1, 

becomes active with positive 

direction and when count > 

Preset 1 and subsequently active 

with negative direction and when 

count < Preset 1  

SUB mode output operations: 

timed signal at Output 1, 

becomes active with negative 

direction and when count < 

Preset 1 and subsequently active 

with positive direction and when 

count > Preset 1  
ADD mode output operations: 

timed signal at Output1, 

becomes passive with positive 

direction and when count > 

Preset 1 and subsequently 

passive with negative direction 

and when count < Preset 1  

SUB mode output operations: 

timed output at Output 1, 

becomes passive with negative 

direction and when count < 

Preset 1 and subsequently 

passive with positive direction 

and when count > Preset 1  
Duration of timed signal of 

Output 1, programmable from 

00.01 to 99.99 s. 

Timed signal is post-triggered 

7.8.6.6  Submenu for Preset 2 

Submenu for Preset 2 
 
 

 

ADD mode output operations: 

permanent signal at Output 2, 

becomes active when count > 

Preset 2  

SUB mode output operations: 

permanent signal at Output 2, 

becomes active when count < 

zero  
ADD mode output operations: 

permanent signal at Output 2, 

becomes passive when count > 

Preset 2  

SUB mode output operations: 

permanent signal at Output 2, 

becomes passive when count < 

zero  

 

ADD mode output operations: 

timed signal at Output 2, 

becomes active when count > 

Preset 2 (Activation only in 

positive direction). 

SUB mode output operations: 

permanent signal at Output 2, 

becomes active when count < 

zero (Activation only in negative 

direction) 

 

ADD mode output operations: 

timed signal at Output 2, 

becomes passive when count > 

Preset 2 (Deactivation only in 

positive direction) 

SUB mode output operations: 

permanent signal at Output 2, 

becomes passive when count < 

zero (Deactivation only in 

negative direction). 

 

ADD mode output operations: 

timed signal at Output 2, 

becomes active with positive 

direction and when count > 

Preset 2 and subsequently with 

negative direction and when 

count < Preset 2  

SUB mode output operations: 

timed signal at Output 2, 

becomes active with negative 

direction and when count < zero 

and subsequently with positive 

direction and when count > zero  

 

ADD mode output operations: 

timed signal at Output 2, 

becomes passive with positive 

direction and when count > 

en

gl

is

h

Seite 15

ADD mode output operations: 

timed signal at Output 1, becomes active when count ≥ Preset 1.

 

(Activation only in positive direction)
SUB mode output operations: 

timed output at Output 1, becomes active when count ≤ Preset 1

 

(Activation only in negative direction)

Summary of Contents for E89005

Page 1: ...Operating instructions Electronic Preset Counter with two presets LCD positive green backlighting relay outputs E89005 7390806 00 09 2017 UK ecomat 200 E89005...

Page 2: ...s 10 5 2 1 Signal and control inputs 10 5 2 2 Supply voltage and outputs 10 6 Operating and display elements 11 6 1 Error message 11 7 Programming 12 7 1 Entering the programming 12 7 2 Choice of main...

Page 3: ...36 8 6 4 Preset 2 37 9 Diagrams 39 9 1 Input modes 39 9 1 1 Pulse counting 39 9 1 2 Timing 41 9 1 3 Frequency meter 42 9 2 Output operations 43 9 2 1 Add modes 43 9 2 2 Sub modes 44 9 2 3 Trail modes...

Page 4: ...Electronic Preset Counter E89005 4 11 13 Connections 50 12 Maintenance repair and disposal 50 13 Approvals standards 51 14 Attachement 51...

Page 5: ...signs used WARNING Warning of serious personal injury Death or serious irreversible injuries may result CAUTION Warning of personal injury Slight reversible injuries may result NOTE Warning of damage...

Page 6: ...Advice concerning the recommended fuseprotection can be found under 11 7 Supply voltage The device is not suitable for use in hazardous areas and for areas excluded in EN 61010 Part 1 3 1 General des...

Page 7: ...or timer to zero adding mode or to preset value 2 subtracting mode The reset input can be inhibited in the programming menu Pulse counter RESET input Timer RESET input Frequency meter no function 3 2...

Page 8: ...ust be set to 6 1 Output 1 Relay with potential free make NO contact or optocoupler with open emitter and collector 6 2 Output 2 Relay with potential free make NO contact or optocoupler with open emit...

Page 9: ...e e g from switchmode power supplies motors clocked controllers or contactors can be reduced by means of appropriate cable routing and wiring Measures to be taken Connect the terminal 2 GND with groun...

Page 10: ...sponse time of the outputs Relays Add Sub Trail 7 ms With automatic repeat 7 ms A B A B A 29 ms 10 3 Tacho Frequency meter Frequency range 0 01 Hz to 65 kHz see section 13 frequencies typ Measuring 76...

Page 11: ...Dynamic reset input re timer to zero adding m subtracting mode The in the programming me Pulse counter RE Frequency meter no Timer RE 5 3 GATE Static gate input functio mode Pulse counter no Frequenc...

Page 12: ...Press key programm Enter the the Prog 7 2 Choice of mai The men the keys Seite 6 7 2 Choice of main menu The menus are selected using T2 next and T1 back 7 1 Entering the p Press the Prog Mod for 3 s...

Page 13: ...at each menu reset key Press the Pressing acknowle causes th to start ag The prev values ar now be c again Pressing selects th programm or For safety switching the relays or optocoupler outputs can b...

Page 14: ...Enter the the Prog 7 2 Choice of mai The men the keys Seite 6 Pressing acknowle terminate modified the EEPR 7 8 Programming 7 8 1 Default paramet Note Th sets have stored th required acknowle paramet...

Page 15: ...t to be changed using the Prog Mode key Briefly activate the MPI NPN or PNP input logic The current count value will be adopted as the new preset value The preset value can subsequently be further mod...

Page 16: ...rail If a tracking preset has been programmed the value for Preset 2 can be set either via the decade keypad or via the Teach In function However the value for Preset 1 must be entered via the decade...

Page 17: ...wert au erhalb Bereichs Seite 16 Set menu item SEtPt to the desired value Briefly activate the MPI NPN or PNP input logic For add output operations the pulse counter or timer will be set to the SEtPt...

Page 18: ...ext SAVE is displayed for 2 s 7 8 Programming Menu 7 8 1 Default parameters Note Three default parameter sets have been permanently stored these can be adapted as required With each acknowledgment of...

Page 19: ...Programming menu Timer Hour meter 7 8 6 Programming menu Tacho Frequency meter 7 8 5 Seite 7 Default setting Parameter set 2 Default setting Parameter set 3 Freely programmable User settings Factory...

Page 20: ...nt Direction INP A count input INP B count direction input uP dn Differential counting A B INP A count input add INP B count input sub uP uP Totalising A B INP A count input add INP B count input add...

Page 21: ...is activated the setting of the preset values and the programming are both inhibited factory settings are highlighted in grey 8 4 2 Mode Submenues for output operations Display Description Submenu Va...

Page 22: ...eset and Total counter Output 2 timed signal active when main counter preset value 2 Automatic reset to zero when main counter preset value 2 Total counter counts all the count pulses from the main co...

Page 23: ...on factor can be programmed from 01 0000 to 99 9999 The setting 01 0000 will not be accepted dp Decimal point setting only optical function 0 no decimal place 0 0 1 decimal place 0 00 2 decimal places...

Page 24: ...ut 1 becomes active when count Preset 1 SUB mode output operations permanent signal at Output 1 becomes active when count Preset 1 ADD mode output operations permanent signal at Output 1 becomes passi...

Page 25: ...becomes passive with negative direction and when count Preset 1 and subsequently passive with positive direction and when count Preset 1 t Out 1 Duration of timed signal of Output 1 Timed signal is po...

Page 26: ...operations permanent signal at Output 2 becomes passive when count Preset 2 SUB mode output operations permanent signal at Output 2 becomes passive when count zero ADD mode output operations timed si...

Page 27: ...of a RESET to zero when adding to preset 2 when subtracting and then starts timing again Timing is stopped with adding operations when preset 2 is reached Timing is stopped with subtracting operation...

Page 28: ...1 Output 2 active when count status 0 Reset to preset 2 AddAr Count mode ADDING with automatic reset Output 1 active when count status preset value 1 Output 2 timed signal active when count status pr...

Page 29: ...he main counter Output 1 active when total counter preset value 1 Manual reset sets both counters to zero Electrical reset only sets the main counter to zero Subtot Count mode SUBTRACTING with automat...

Page 30: ...al places 0 000 3 decimal places SetPt Set value 000000 Factory setting 000000 999999 Set value can be programmed from 000000 to 999999 A previously programmed decimal point will be displayed CoLor Di...

Page 31: ...ations permanent signal at Output 2 becomes passive when count zero ADD mode output operations timed signal at Output 2 becomes active when count Preset 2 Activation only in positive direction SUB mod...

Page 32: ...n ADD mode output operations timed signal at Output 2 becomes passive when count Preset 2 Deactivation only in positive direction SUB mode output operations permanent signal at Output 2 becomes passiv...

Page 33: ...tion SUB mode output operations permanent signal at Output 2 becomes passive when count zero Deactivation only in negative direction ADD mode output operations timed signal at Output 2 becomes active...

Page 34: ...al measurement A B Inp A frequency input A Inp B frequency input B AAdd b Total measurement A B Inp A Frequency input A Inp B Frequency input B quAd Frequency measurement with direction recognition Qu...

Page 35: ...be programmed from 00 0001 to 99 9999 The setting 00 0000 will not beaccepted diViSo Division factor 01 0000 Factory setting 01 0000 99 9999 Division factor can be programmed from 01 0000 to 99 9999 T...

Page 36: ...eset 2 see also section 17 Output operations Tracking Preset mode with automatic reset When preset 2 is changed then preset 1 automatically tracks it Reset to zero Automatic reset to zero when main co...

Page 37: ...s passive when count Preset 1 Deactivation only in negative direction ADD mode output operations timed signal at Output1 becomes active with positive direction and when count Preset 1 and subsequently...

Page 38: ...med signal at Output 1 becomes active when count Preset 1 Activation only in positive direction SUB mode output operations timed output at Output 1 becomes active when count Preset 1 Activation only i...

Page 39: ...Inp A Count input add Inp B Count input sub Add Display 0 Preset Sub Display Preset 0 Up Up Inp A Count input 1 add Inp B Count input 2 add Add Display 0 Preset Quad A 90 B Inp A Count input Count on...

Page 40: ...ng edge Quad 4 A 90 B Inp A Count input Count on rising and on falling edges Inp B Count input Count on rising and on falling edges Reverse direction Add Display 0 Preset Sub Display Preset 0 A B Inp...

Page 41: ...B Start Stop Add Display 0 Preset Sub Display Preset 0 FrRrun 15 Input modes Timing Function Diagram PNP Count on rising edge NPN Count on falling edge InA InB Inp A Start Inp B Stop Add Display 0 Pre...

Page 42: ...ut 2 Formula A B A x100 english Seite 23 Inp A Frequency input 1 Inp B Frequency input 2 Formula A B Quad 16 Input modes Frequency meter Function Diagram PNP Count on rising edge NPN Count on falling...

Page 43: ...eite 24 AddTot 17 Output operations Mode Diagram Mode Diagram Only in the mode and Additionally in the mode and Add Sub AddAr SubAr AddBat SubBat AddTot SubTot Seite 24 17 Output operations Mode Diagr...

Page 44: ...tput operations Mode Diagram Mode Diagram Only in the mode and Additionally in the mode and Add Sub only in this modes 17 Output operations Mode Diagram Mode Diagram Only in the mode and Additionally...

Page 45: ...UK Electronic Preset Counter E89005 45 9 2 3 Trail modes Mode Diagram Trail Mode Diagram Trail TrailAr TrailAr Mode Diagram Trail TrailAr Seite...

Page 46: ...Electronic Preset Counter E89005 46 10 Dimensions 18 Dimensional Drawings Panel cut out Seite 26 E89005 18 Dimensional Drawings Panel cut out Seite 26 Panel cut out...

Page 47: ...29 ms Frequencies typical 13 Frequencies typical 13 1 Pulse counter HTL level AC supply typ Low 2 5 V typ High 22 V Add Sub Trail AddAr SubAr AddBat SubBat TrailAr AddTot SubTot Cnt Dir 55 kHz 2 8 kHz...

Page 48: ...with AC supply HTL level Low 0 4 VDC High 12 30 VDC english Seite 19 11 4 Timer Seconds 0 001 999 999 s Minutes 0 001 999 999 min Hours 0 001 999 999 h h min s 00h 00min 01s 99h 59min 59s Min time me...

Page 49: ...itching capacity max 750 VA 90 W Mechanical switching cycles 2 x 106 N of switching cycles 5 x 104 at 3 A 250 V AC N of switching cycles 5 x 104 at 3 A 30 V DC 11 7 Supply voltage Supply voltage 90 26...

Page 50: ...on Shock resistance EN 60068 2 27 100 g XYZ 3 times in each directio Cleaning The front of the unit should only be cleaned using a soft damp water cloth 11 13 Connections Supply voltage and relay outp...

Page 51: ...UK Electronic Preset Counter E89005 51 13 Approvals standards The EC declaration of conformity and approvals can be found at www ifm com 14 Attachement Parameter structure see next pages...

Page 52: ...Er on T2 T2 MPi tEAch MPi SEt Loc InP PrG PrE Loc InP ProG T2 T2 P ModE ModE Add P ModE Sub ModE AddAr ModE SubAr ModE AddbAt ModE SubbAt ModE Addtot ModE Subtot ModE trAiL ModE tr_Ar T2 ConFiG P rESm...

Page 53: ...P PrESET P P P P P InP PoL nPn T2 FiLtEr on T2 StArt Inb Inb StArt FrErun StArt Auto T2 GAtE GAtE hi T2 MPi tEAch MPi SEt Loc InP PrG PrE Loc InP ProG T2 T2 P ModE ModE Add P ModE Sub ModE AddAr ModE...

Reviews: