33
☞
Check the exit button operation.
1. Check the condition of the connection cable (a short circuit or cut) between and the
100R.
2. Connect two wires from the exit button.
- If the FACE007 operates when the exit button is pressed.
Replace the exit button.
- If the FACE007 does not respond.
Initialize the product
#1)
.
1
●
If the problem still persists, contact our customer service center.
●
Problem
Your RF card is successfully recognized by an exit reader, but the RF card data is not
transferred to a computer or other data is transferred.
●
Cause
▶
A connectivity error between the exit reader and the 100R
▶
A communication error between the exit reader and the 100R
▶
An exit reader error
▶
System malfunction/data damaged or lost due to an external noise or a short circuit
#1)
System Initialization: See page 24 of this manual.
#2)
Initial Setting: See page 10 of this manual.
#3)
Setting Changes: See page 14 of this manual.
#5)
Installation: See page 6 of this manual.
Make sure to use a NO (Normal Open)-type exit button.
Caution
Upon initialization, all data default value will be restored.
Caution
See “Installation
#5)
” to connect the exit button.