VI
FAULT DIAGNOSE AND TREATMENT
This part introduce fault diagnose and treatment.
Note: Certain circuits have lethal high voltages that allow only professional technicians to
perform maintenance operations on the unit. Special care must be taken when
troubleshooting with power on.
See Table 7-1 for fault diagnosis and treatment of each component.
Figure 7-1 Trouble shooting of compressor and cooling system
ERRO
CODE
Fault name
Reasons
Measures
F2
Inlet water temp Twi
sensor fault
1. The interface between
the sensor and the main
board is loose or detached.
2. The sensor probe comes
off.
3. The sensor connection
line is open or shorted.
4. The sensor is damaged.
1. Check and reinforce the
interface between the sensor and
the main board.
2. Re-fix the sensor probe.
3. Repair the sensor cable.
4. Replace the sensor.
F3
Liquid pipe temp
sensor fault
1. The interface between
the sensor and the main
board is loose or detached.
2. The sensor probe comes
off.
3. The sensor connection
line is open or shorted.
4. The sensor is damaged.
1. Check and reinforce the
interface between the sensor and
the main board.
2. Re-fix the sensor probe.
3. Repair the sensor cable.
4. Replace the sensor.
F4
Outlet water temp
Two sensor fault
1. The interface between
the sensor and the main
board is loose or detached.
2. The sensor probe comes
off.
3. The sensor connection
line is open or shorted.
4. The sensor is damaged.
1. Check and reinforce the
interface between the sensor and
the main board.
2. Re-fix the sensor probe.
3. Repair the sensor cable.
4. Replace the sensor.
F1
Tw temp sensor fault
(reserved)
1. The interface between
the sensor and the main
board is loose or detached.
2. The sensor probe comes
off.
1. Check and reinforce the
interface between the sensor and
the main board.
2. Re-fix the sensor probe.
3. Repair the sensor cable.