- 43 -
D32
Maximum speed 4 of DC motor under
cooling mode
0~1000
T
<
25
℃
500
D33
Heating valve function selection
(stand by )
0 not allowed /
1 allow to turn on
1
D34
Four-way valve polarity
0: Power on when
cooling 1: Power on
when heating
0
D35
The ambient temp when electric heating turns
on
-30
℃
~20
℃
-5
℃
D36
How water setting max. parameter
20
℃
~60
℃
55
D37
Cooling water setting Min. parameter 5
℃
~30
℃
12
D38
Heaitng water setting Max. parameter 20
℃
~60
℃
50
Note: The parameters B04 and B06 are actually divided by 10 (that is, the range is 0.1~0.6)
4. "
" minus key
When powering on, in the main interface, single press "
" to adjust the current mode setting temperature;
In the main interface, long press the "
" key for 3 seconds to enter the unit status parameter query, cooperate
with the "
" and "
" keys to browse the parameters, and press the "
" key to exit the parameter query.
Machine status table 1: Long press
Key for 3 seconds
Query code
Description
Display range
01
Inlet water temp
-30~99
℃
02
Outlet water temp
-30~99
℃
03
Ambient temp
-30~99
℃
04
Exhaust temp
0~125
℃
05
Suction temp
-30~99
℃
06
External coil temp
-30~99
℃
07
Economizer inlet temp
-30~99
℃
08
Economizer outlet temp
-30~99
℃
09
Cooling coil temp
-30~99
℃
10
Water tank temp
-30~99
℃
11
Main EEV temp
12
Auxiliary EEV temp
13
Compressor current
14
Heat sink temp
15
DC bus voltage value
Summary of Contents for ISW-10 SF1-DN1
Page 21: ... 21 XD 05BSPM ...
Page 56: ... 56 By sliding the button you can adjust the setting parameters Function buttons ...