- 37 -
B02
Auxiliary EEV manual steps
20~450
350
B03
EVI electromagnetic expansion valve
turn on temp
11
℃
~45
℃
11
℃
B04
Auxiliary EEV exhaust proportional
coefficient
1~6
2
B05
Auxiliary EEV exhaust differential
coefficient
0~180
1
B06
Auxiliary EEV superheat proportional
coefficient
1~6
2
B07
Auxiliary EEV superheat differential
coefficient
0~180
1
B08
Auxiliary EEV adjustment cycle
10~20
15
B09
Auxiliary EEV target exhaust temp
70~120
90
B10
Close auxiliary EEV exhaust temp
40~70
60
B11
Auxiliary EEV heating target
superheat 1
-10~10
4 T≥14
℃
B12
Auxiliary EEV heating target
superheat 2
-10~10
4 [9
,
14)
B13
Auxiliary EEV heating target
superheat 3
-10~10
4 [4
,
9)
B14
Auxiliary EEV heating target
superheat 4
-10~10
4 [-5
,
4)
B15
Auxiliary EEV heating target
superheat 5
-10~10
4 [-10
,
-5)
B16
Auxiliary EEV heating target
superheat 6
-10~10
4 [-16
,
-10)
B17
Auxiliary EEV heating target
superheat 7
-10~10
4 [-23
,
-16)
B18
Auxiliary EEV heating target
superheat 8
-10~10
4 T
<
-23
℃
B19
Auxiliary EEV heating initial opening
00
0~480
0
Ambient tempT≥14
℃
B20
Auxiliary EEV heating initial opening
01
0~480
10
[9
,
14)
B21
Auxiliary EEV heating initial opening
02
0~480
30[4
,
9)