- 46 -
R16
Exhaust setting TP0
50~125
℃
95
℃
R17
Exhaust setting TP1
50~125
℃
100
℃
R18
Exhaust setting TP2
50~125
℃
105
℃
R19
Exhaust setting TP3
50~125
℃
110
℃
R20
Exhaust setting TP4
50~125
℃
120
℃
R21
Lower limit of FM point 01
0~125Hz
125
R22
Lower limit of FM point 02
0~125Hz
125
R23
Lower limit of FM point 03
0~125Hz
125
R24
Lower limit of FM point 04
0~125Hz
125
R25
Upper limit of FM point 01
0~125Hz
125
R26
Upper limit of FM point 02
0~125Hz
125
R27
Upper limit of FM point 03
0~125Hz
125
R28
Upper limit of FM point 04
0~125Hz
125
8. Restore factory settings
In the shutdown state, press and hold the "
" key + "
" key + "
" key + "
" key at the same time for 3
seconds to restore the factory setting parameters by wire control. At this time, the buzzer will sound twice in
succession, and all the parameter values will return to the default value.
5.4 FAULT CODE/ SYSTEM PROTECTION
Fault
code
Description Reason
Solution
Er 03 Water flow fault
1.The water system is blocked;
2.Improper installation of the inlet and
outlet water temperature sensor detection
position leads to inaccurate detection of
water temperature;
3,The pump size is inappropriate
1. Clean the water pipe;
2. Check whether the probe position of the inlet
and outlet water temperature sensor is
correctly installed and reinforced;
3.Change the water pump;
Er 04
Anti-freezer in
winter
The ambient temperature is lower than the
antifreeze setting value.
1. Start the antifreeze cycle and start the
antifreeze protection.
2. Drain the internal water and shut down if you
don't use it for a long time .