- 45 -
6. Forced defrosting:
Press the "
" and "
" keys to enter the forced defrost mode.
When entering defrost, "
" is displayed.
7. Frequency parameter setting
Long press the "
" + "
" key for 5 seconds to enter the password input state, the time display position
displays "0000", press the "
" or "
" key to enter the password, and then press the "
" key to switch the
password digits. When the last password is entered , And then press "
" to confirm the password.
Enter the 4-digit password "9615", and enter the manual frequency setting state after the input is completed,
directly press the "
" "
" keys on the main page to adjust the manual frequency.
Enter the 4-digit password "8866", and enter the frequency view state after the input is completed, the original
"hour" displays "target frequency", and the original "minute" displays "operating frequency".
Enter the 4-digit password "4180", after the input is completed, the buzzer will beep twice and enter the
frequency conversion parameter setting
◎
Frequency parameter table: long press [
] + [
], enter "4180"
Code
Parameter name
Adjustment
range
default
Remark
R00
Hot water frequency 1
30~120Hz
60 Hz
T≥25
℃
R01
Hot water frequency 2
30~120Hz
60 Hz
[10
,
25)
R02
Hot water frequency 3
30~120Hz
75 Hz
[-10
,
10)
R03
Hot water frequency 4
30~120Hz
80 Hz
T
<
-10
℃
R04
Heating frequency 1
30~120Hz
60 Hz
T≥14
℃
R05
Heating frequency 2
30~120Hz
70 Hz
[9
,
14)
R06
Heating frequency 3
30~120Hz
75 Hz
[4
,
9)
R07
Heating frequency 4
30~120Hz
75 Hz
[-5
,
4)
R08
Heating frequency 5
30~120Hz
80 Hz
[-10
,
-5)
R09
Heating frequency 6
30~120Hz
80 Hz
[-16
,
-10)
R10
Heating frequency 7
30~120Hz
85 Hz
[-23
,
-16)
R11
Heating frequency 8
30~120Hz
85 Hz
T
<
-23
℃
R12
Cooling frequency 1
30~120Hz
75 Hz
T≥38
℃
R13
Cooling frequency 2
30~120Hz
70 Hz
[30
,
38)
R14
Cooling frequency 3
30~120Hz
70 Hz
[25
,
30)
R15
Cooling frequency 4
30~120Hz
65 Hz
T
<
25
℃
Summary of Contents for ISW-10 SF1-DN1