1. To ensure the normal operation of the unit, try to choose a spacious space as the installation site of
the unit;
2. Avoid placing multiple outdoor units close together to avoid cross-air flow, unbalanced loads, and
competitive operation;
3
.
When installing on the top of the building, pay attention to protecting the waterproof layer and
complying with relevant local regulations.
2.11 MAINTENANCE SPACE REQUIREMENTS
1.There is no obstruction within 2m of the air outlet of the unit.
2.Both sides of the unit need to ensure a maintenance space of more than 600mm.
2.12 INSTALLATION STEPS
The installation steps of the outdoor unit are as follows:
1. Make the mounting base according to the requirements of the outline drawing. The mounting base can
be made by the user.
2. Determine the installation position, and fix the installation base to the selected installation position
according to the site conditions and user requirements.
3. Use nuts, spring washers, flat washers and bolts to fix the unit on the mounting base.
4.During installation, it can be slightly inclined to the drainage side to facilitate drainage.
5. Install on a firm foundation.
2.13 INSTALL UNIT PIPE
1.Please refer to the water system layout drawing for connecting the unit's water system pipeline.
2.14 INSPECTION ITEMS AFTER MECHANICAL INSTALLATION IS
COMPLETED
1.Leave some space around the equipment for easy maintenance;
2.The unit is placed horizontally and the installed fastening parts are locked;
3.The pipelines connected to the unit have been installed and all valves have been fully opened;
4.The drain pipe is connected;
5.All pipe joints have been tightened;
6.After the installation of the equipment is completed, the debris inside or around the equipment has
been removed (such as transportation materials, structural materials, tools, etc.);
After all the contents have been checked and confirmed, please perform the electrical installation