- 41 -
B67
difference
0~125
℃
34
℃
[-5
,
4)
B68
Auxiliary EEV heating exhaust temp
0~125
℃
40
℃
[-10
,
-5)
B69
difference
0~125
℃
40
℃
[-16
,
-10)
B70
Auxiliary EEV heating exhaust temp
0~125
℃
40
℃
[-23
,
-16)
B71
difference
0~125
℃
40
℃
T
<
-23
℃
B72
Auxiliary EEV hot water exhaust temp
difference
0~125
℃
35
℃
T≥25
℃
B73
Auxiliary EEV hot water exhaust temp
difference
0~125
℃
35
℃
[10
,
25)
B74
Auxiliary EEV hot water exhaust temp
difference
0~125
℃
35
℃
[-10
,
10)
B75
Auxiliary EEV hot water exhaust temp
difference
0~125
℃
35
℃
T
<
-10
℃
B76
Control mode of auxiliary EEV
0Enthalpy
superheat
/1 exhaust super
heat
0
C01
Water pump mode 1,non-stop;0,stop 0~1
1
( it is effective for heating
And cooling mode)
C02
Pressure sensor
:
1 effective/ 0 invalid 0~1
0
C03
High pressure protection value
25.0-50.0bar
42.0bar
C04
High pressure recovery value
25.0-50.0bar
36.0bar
C05
Low pressure protection value
0-20.0bar
0.5bar
C06
Low pressure recovery value
0-20.0bar
1.5bar
D01
AC wind speed switching ambient temp -10~50
℃
28
D02
AC wind speed switching ambient temp -10~50
℃
26
D03
Maximum speed 1 of DC motor under
heating
0~1000
T≥14
℃
400
D04
Maximum speed 2 of DC motor under
heating
0~1000
[9
,
14) 700
D05
Maximum speed 3 of DC motor under
heating
0~1000
[4
,
9) 800
D06
Maximum speed 4 of DC motor under
heating
0~1000
[-5
,
4) 900
D07
Maximum speed 5 of DC motor under 0~1000
[-10
,
-5) 900