5. Setting up the device
23
Menu level
Parameterisation level
Bargraph,
Ba.src:
Default:
actua
With this function the following values can be allocated to the display: the current measurand,
the min/max value, the totaliser value, the process-controlled hold value, the sliding average
value, the constant value or the difference between constant and current value of the bargraph.
With
[P]
the selection is confirmed and the device changes into menu level.
Adjusting the final value of the bargraph,
ba.ENd:
Default:
10000
Set the final value from the smallest to the highest digit with
[
▲
] [
▼
]
and confirm each digit
with
[P]
. A minus sign can only be parameterized on the highest value digit. After the last digit,
the display switches back to the menu level.
Adjusting the initial value of the bargraph,
ba.off:
Default:
0
Set the initial value from the smallest to the highest digit with
[
▲
] [
▼
]
and confirm each digit
with
[P]
. A minus sign can only be parameterized on the highest value digit. After the last digit,
the display switches back to the menu level.
Selection of the bargraph functions,
ba.fct:
Default:
bar.fo
The bargraph can be displayed with the following possibilites: bars forwards, bars backwards,
bars from the middle, a dot display of the bargraph or a dot display with a permanently
displayed midpoint. Confirm the selection by pressing the
[P]
button. The display then switches
back to the menu level again.
Menu group level
5.4.3. Bargraph functions
Menu level