5. Setting up the device
Menü-Ebene
Parameter-Ebene
Selection of analog output,
Out.rA:
Default:
4-20
Three output signals are available: 0-10 VDC, 0-20 mA and 4-20 mA, with this function, the
demanded signal is selected.
Setting up the final value of the analog output,
Out.En:
Default:
10000
The final value is adjusted from the smallest digit to the highest digit with
[
▲
] [
▼
]
and digit by
digit confirmed with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit, the device changes back into menu level.
Setting up the initial value of the analog output,
Out.OF:
Default:
00000
The final value is adjusted from the smallest digit to the highest digit with
[
▲
] [
▼
]
and digit by
digit confirmed with
[P]
. A minus sign can only be parametrised on the highest digit. After the
last digit, the device changes back into menu level.
Threshold values / limit values,
LI-1:
Default:
2000
For both limit values, two different values can be parameterized. With this, the parameters for
each limit value are called up one after another.
Hysteresis for limit values,
HY-1:
Default:
00000
The delayed reaction of the alarm is the difference to the threshold value, which is defined by
the hysteresis.