5. Setting up the device
19
Menu level
Parameterisation level
Dynamic for the sliding average determination,
step:
Default:
no
With
step
the sliding average determination can be adjusted dynamically. If 6pro or 12pro was
selected, a frequency value with a variance of 6% or 12% of the current display value is taken
over directly for the sliding averaging. The display appears to be more dynamic at a fast
frequency change, without appearing disturbed by a slightly unsteady frequency.
Zero point slowdown,
ZErO:
Default:
00
At the zero point slowdown, a value range around the zero point can be preset, so the display
shows a zero. If e.g. a 10 is set, the display would show a zero in the value range from -10 to
+10; below continue with -11 and beyond with +11. The maximum adjustable range of value is
99.
Definite contstant value,
const
:
Default:
0
The constant value can be evaluated via the alarms or via the analog output, like the current
measurand. The decimal place cannot be changed for this value and is taken over by the
current measurand. Like this a setpoint generator can be realised via the analog output by this
value. Furthermore it can be used for calculating the difference. At this the constant value is
substracted from the current measurand and the difference is evaluated in the alerting or by the
analog output. Thus regulations can be displayed quite easily.
Minimum constant value,
con.mi
:
Default:
-i9999
The minimum constant value is adjusted from the smallest to the highest digit with the
navigation keys
[
▲
] [
▼
]
and confirmed digit per digit with
[P]
. A minus sign can only be
adjusted on the highest digit. After the last digit the display changes back into menu level.
Maximum constant value,
con.ma
:
Default:
99999
The maximum constant value is adjusted from the smallest to the highest digit with the
navigation keys
[
▲
] [
▼
]
and confirmed digit per digit with
[P]
. A minus sign can only be
adjusted on the highest digit. After the last digit the display changes back into menu level.