5. Setting up the device
18
5.4.2. General device parameters
Menu level
Parameterisation level
Display time,
DISEC:
Default:
01.0
The display is set up with
[
▲
] [
▼
]
. Thereby you switch until 1 second in 0.1 steps and until
10.0 seconds in 1.0-steps. With
[P]
the selection is confirmed and the device changes into
menu level.
Rounding of display values,
round:
Default:
00001
This function is for instable display values, where the display value is changed in increments of
1, 5, 10 or 50. This does not affect the resolution of the optional outputs. With
[P]
the selection
is confirmed and the device changes into menu level.
Arithmetic,
ArItH:
Default:
no
With this function the calculated value, not the measuring value, is shown in the display. With
no
, no calulation is deposited. With
[P]
the selection is confirmed and the device changes into
menu level.
Sliding average determination,
AVG:
Default:
1.0
Here, the number of the meterings that need to be averaged is preset. The time of averaging
results of the product of measuring time
SEC
and the averaged metering
AVG
. With the selection
of
AVG
in the menu level
DISPL,
the result will be shown in the display and evaluated via the
alarms
AL1-Al4
or via the analog output
Outpt
.
Menu group level
Menu level
then
Reciprocal
Root extraction
Square