5. Setting up the device
32
Menu level
Parameterisation level
Function for threshold value undercut/exceedance,
Fu-1:
Default:
high
A limit value undercut is selected with
Louu
(for LOW = lower limit value), a limit value
exceedance with
High
(for HIGH = higher limit value). If e.g. limit value 1 is on a threshold level
of 100 and allocated with function
High
, an alarm is activated by reaching the threshold level. If
the threshold value was allocated to
Low,
an alarm will be activated by undercutting the
threshold value, as long as the hysteresis is zero.
Switching-on delay,
ton-1:
Default:
000
For limit value 1 one can preset a delayed switching-on of 0-100 seconds.
Switching-off delay,
toF-1:
Default:
000
For limit value 1 one can preset a delayed switching-off of 0-100 seconds.
Back to menu group level,
rEt
:
With
[P]
the selection is confirmed and the device changes into menu group level
„–Al1–“
.
The same applies for
Al2
to
al8
.