User response:
Complete the following steps until the problem is solved:
1.
Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
80070101-2c03ffff
Sensor Mezz Exp 3 temp has transitioned from normal to non-critical state.
Explanation:
The temperature of the I/O expansion adapter in I/O expansion connector 3 has exceeded its specified
threshold.
May also be shown as 800701012c03ffff or 0x800701012c03ffff
Severity:
Warning
Alert Category:
Warning - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0520
SNMP Trap ID:
12
Automatically notify Support:
No
User response:
Complete the following steps until the problem is solved:
1.
Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
80070101-2c04ffff
Sensor Mezz Exp 4 temp has transitioned from normal to non-critical state.
Explanation:
The temperature of the I/O expansion adapter in I/O expansion connector 4 has exceeded its specified
threshold.
May also be shown as 800701012c04ffff or 0x800701012c04ffff
Severity:
Warning
Alert Category:
Warning - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0520
SNMP Trap ID:
12
Automatically notify Support:
No
User response:
Complete the following steps until the problem is solved:
1.
Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2.
Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
80070101-2d01ffff
Sensor PCH Overtemp has transitioned from normal to non-critical state.
Explanation:
The temperature of the Platform Controller Hub (PCH) has exceeded its specified threshold.
May also be shown as 800701012d01ffff or 0x800701012d01ffff
Severity:
Warning
Alert Category:
Warning - Temperature
Serviceable:
Yes
80070101-2c03ffff • 80070101-2d01ffff
Chapter 6. Troubleshooting
113
Summary of Contents for Flex System x440 Compute Node
Page 1: ...IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Page 2: ......
Page 3: ...IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Page 34: ...22 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Page 50: ...38 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Page 68: ...56 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Page 498: ...486 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Page 570: ...558 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Page 578: ...566 IBM Flex System x440 Compute Node Types 7917 and 2584 Installation and Service Guide ...
Page 583: ......
Page 584: ... Part Number 81Y1144 Printed in USA 1P P N 81Y1144 ...