Safety
Figure
0-10. Ground Wire Connection
This operation must be performed before any network connection.
Note: All the previous measurements should indicate 0.1 ohm or less.
e
Building Grounding
Check that there is less than 1 V ac between the metal housings of plugs, connec-
tors, receptacles, and so on., and any grounded point in the building. This can be
any grounded metal structure, such as the stanchions of a raised floor (if they are
electrically connected to building ground), a metal water pipe, building steel, and so
on.
Notes:
1) When probing a painted metal part, ensure that the meter probe tip penetrates the
paint.
2) Also check plugs of incoming cables.
5
Circuit Breaker and Protector Rating
Refer to Table 0-4 on page xxx for CB and CP locations.
Check that:
All CBs and CPs in the 3745 and 3746-900 are rated at the indicated value in Table 0-4 on
page xxx. If the rating is not indicated, check the part number against one of the following:
–
IBM 3745 Communication Controller Models 130 to 17A, Parts Catalog, S135-2012
–
IBM 3746 Expansion Unit Model 900, Parts Catalog, S135-2013
–
IBM 3746 Nways Multiprotocol Controller Models 900 and 950, Parts Catalog, S135-2015.
The fuses in the controller expansion ac outlet distribution box must be 7 A, 250 V slow
(PN 58G5782).
6
Input Power Voltage
The power rating plate indicates the voltage range available (200/220/240) and the frequency
(50/60 Hz).
3745 Input Power voltage
The voltage label (label J) indicates the input voltage for which the 3745 is wired. This information
must be in accordance with Switch 1 on PS2.
Performing a power conversion Inspection.
A power conversion inspection must be performed on any 3745 Communication Controller that
has been converted from 50 Hz to 60 Hz, or from 60 Hz to 50 Hz.
The following is used only for the primary power box. Refer to Figure 4-1 on page 4-3 for
location.
Check Table 0-1 on page xxviii for the correct part numbers for the specified 50 Hz or 60 Hz
use. In case of discrepancy, contact your support structure.
Safety
xxvii
Summary of Contents for 3745 130
Page 2: ......
Page 10: ...viii 3745 Models 130 to 17A MIP ...
Page 16: ...xiv 3745 Models 130 to 17A MIP ...
Page 23: ...Safety Figure 0 2 Ground Wire Connection on Controller Expansion Safety xxi ...
Page 46: ...Safety xliv 3745 Models 130 to 17A MIP ...
Page 47: ...Safety Safety xlv ...
Page 48: ...Safety xlvi 3745 Models 130 to 17A MIP ...
Page 49: ...Safety Safety xlvii ...
Page 50: ...Safety xlviii 3745 Models 130 to 17A MIP ...
Page 51: ...Safety Safety xlix ...
Page 52: ...Safety l 3745 Models 130 to 17A MIP ...
Page 53: ...Safety Safety li ...
Page 54: ...Safety lii 3745 Models 130 to 17A MIP ...
Page 55: ...Safety Safety liii ...
Page 56: ...Safety liv 3745 Models 130 to 17A MIP ...
Page 57: ...Safety Safety lv ...
Page 58: ...Safety lvi 3745 Models 130 to 17A MIP ...
Page 66: ...Safety lxiv 3745 Models 130 to 17A MIP ...
Page 68: ...Preface lxvi 3745 Models 130 to 17A MIP ...
Page 70: ...Amendments lxviii 3745 Models 130 to 17A MIP ...
Page 154: ...3745 MAPs 1 84 3745 Models 130 to 17A MIP ...
Page 200: ...Service Processor MAPs 2 46 3745 Models 130 to 17A MIP ...
Page 226: ...Diagnostics 3 26 3745 Models 130 to 17A MIP ...
Page 253: ...FRU Exchange Location 01S Figure 4 31 3745 EPO Chapter 4 3745 FRU Exchange 4 27 ...
Page 332: ...CE leaving procedure 4 106 3745 Models 130 to 17A MIP ...
Page 338: ...Maintenance Aids A 6 3745 Models 130 to 17A MIP ...
Page 354: ...Abbreviation X 6 3745 Models 130 to 17A MIP ...
Page 359: ......
Page 360: ...IBM Part Number 03F5017 Printed in Denmark by IBM Danmark A S ð3F5ð17 SY33 2ð7ð ð9 ...