390
Appendix
Zone output
A signal can be output when the actuator has entered a desired zone specified by the user.
Three parameters must be set to specify a zone.
A zone is set for each axis.
No.
Parameter name
Default value
Input range
Unit
86 Zone 1 MAX
0
-99999999 ~ 99999999
0.001 mm
87 Zone 1 MIN
0
-99999999 ~ 99999999
0.001 mm
88 Zone 1 output number
0
0 ~ 899
None
Axis-specific parameter No. 86, “Zone 1 MAX”
Set the maximum limit of the zone, in units of 0.001 mm.
Example: To set 50 mm, set the value “50000.”
Axis-specific parameter No. 87, “Zone 1 MIN”
Set the minimum limit of the zone, in units of 0.001 mm.
Example: To set 10 mm, set the value “10000.
Axis-specific parameter No. 88, “Zone 1 output number”
Set an output port or flag number for the zone.
The output number set in this parameter cannot be used in programs.
Note
Set the zone so that the passing time through the zone will become at least 3 msec.
(Axis-specific
parameter No. 86)
MAX side
Set an output range.
(A signal is output while the actuator is
passing through this range.)
Passing status ON
(Axis-specific parameter No. 88)
MIN side
(Axis-specific
parameter No. 87)
Actuator