317
Part 3 Positioner Mode
5.3 Movements
through
Positions
Timings of how the actuator moves through positions are illustrated below.
Timing Chart of Movement through Positions (Standard Positioner Mode)
T
1
: At least 6 msec
Operate the actuator to move through positions by following the procedure explained below.
* Confirm beforehand that the positioning complete output signal, home-return complete output signal
and servo-ON status output signal are all ON.
[1] Change the previous position number input to a different position number.
[2] Turn ON the start input signal.
[3] Confirm that the positioning complete output signal is OFF.
[4] Turn OFF the start input signal.
[5] Confirm that the positioning complete output signal is ON.
Repeat steps [1] through [5] sequentially.
*Pause and *cancellation inputs are contact-B input signals (always ON), so keep these signals ON while
the actuator are moving through the specified positions.
Input
Output
Start
Home return
Position input
Alarm
Ready
Positioning complete
Home return complete
Servo ON status