6.4 Parameter function descriptions
6-9
6. Parameters
Parameter No.4: Home position adjustment
No. Category
Name
Symbol
Unit Input
range
Default setting
at shipping
4 B
Home position
adjustment
OFST
mm
0.01 to 9999.99
According to
ELECYLINDER
specifications
●
Sets the distance between the home side mechanical stopper and the home position.
●
The minimum setting unit is 0.01mm.
●
Adjustment with this parameter is possible in the following situations.
(1) To match the ELECYLINDER home position and the mechanical home position after assembly
into equipment.
(2) To adjust the new home position upon reversing the default home return direction after purchase.
(3) To eliminate a slight deviation from the previous home position generated after replacing the
ELECYLINDER.
If [Parameter No.4] is [0.30mm],
the relationship between mechanical stopper and home position is as follows.
Caution
If adjusting Parameter No.4, simultaneously adjust Parameter No.1.
Operation range adjustment with parameter No.1 uses the home position as reference.
Do not set Parameter No.4 to a value smaller than the default setting at shipping.
This may result in abnormal home return operation, alarm triggering or abnormal
operation. If the value must be set small, please contact IAI.
After changing this parameter, always perform home return reset (absolute reset).
Configuration example
0.30mm
0.30mm
80.00mm
(Stroke to be used)
Parameter No.4: 0.30mm
Home position
Summary of Contents for EC-R6
Page 9: ......
Page 28: ...Intro 19 ...
Page 130: ...1 100 1 Specifications ...
Page 202: ...2 70 2 Installation ...
Page 218: ...3 15 3 Wiring ...
Page 240: ...4 21 4 Operation ...
Page 328: ...9 15 9 External Dimensions ...
Page 336: ...11 3 11 Warranty ...
Page 337: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 7 ELECYLINDER Chapter12 ...
Page 346: ......
Page 347: ......