address is set in binary coding format in the range of 1–63. The first bit is the least
significant, and the sixth bit is the most significant. ON indicates 1 and OFF
indicates 0. The address range is 1–63.
NO TE
The numbers indicate the DIP switch settings of the T/H sensors.
Figure 3-26 DIP switch settings for T/H sensors
Step 3 Connect the communications cables to the T/H sensors.
Figure 3-27 Cable connections to T/H sensors
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
3 Installing Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
36