Parameter
Description
Device Address
Address set on the device. The default value is 0.
Timeout Period
Timeout duration for a connection test. The default value is
3s.
Step 8 Click
on the toolbar to save the device information.
Step 9 Click Connection test to start the connection test.
Step 10 Click Bind AccessController and select an access controller to bind the fingerprint
controller and select a door passage for the access controller from respective drop-
down menus.
----End
6.5.4 Adding a Smart Cooling Product
6.5.4.1 Setting Monitoring Parameters for Smart Cooling Products (over
Modbus-RTU)
The method of setting monitoring parameters for NetCol5000-C(065, 080),
NetCol5000-C025/C030/A020/A035/A050, NetCol8000-A050/A060/A100/A120/
C070/C150, and FusionCol8000-E220/E400/C080/C210 are the same. This section
describes the configuration method for the NetCol5000.
Prerequisites
●
The device address planned for the NetCol5000 is obtained.
●
The NetCol5000 is powered on.
●
The IP address, user name, and password for logging in to the collector are
obtained.
●
A PC with an IP address in the same network segment as the collector is
prepared, and the PC connects to the collector over a switch.
NO TE
The Modbus TCP protocol is recommended for connecting FusionCol8000-E/FusionCol8000-
C series smart cooling products to the NetEco.
Context
Before connecting the NetCol5000 to the NetEco, set monitoring parameters, such
as the device address and baud rate, on the NetCol5000, and then modify the port
parameters for the collector connecting to the NetCol5000 to ensure that the
values of BaudRate, DataBit, StopBit, and Parity on the NetCol5000 are
consistent with those for the collector port.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
263