(1) UIM20A expansion module (2) T/H sensor
(3) NTC sensor
----End
3.7.7 Installing a Region-type Water Sensor
Context
A water sensor consists of a water detection cable, water detector, and conversion
cable. The water detection cable is laid out on the floor, connecting to the water
detector placed near the collector by the conversion cable.
Figure 3-28 Water sensor components
(1) Water detector
(2) Conversion cable end A,
connecting to the water
detector
(3) Conversion cable
(4) Conversion cable end B,
connecting to the water
detection cable
(5) Water detection cable end
A, connecting to the
conversion cable
(6) Water detection cable
Procedure
Step 1 Install the water detector near the collector and secure it using screws or other
methods.
Step 2 Connect the water detection cable to the conversion cable.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
3 Installing Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
37