6.4.5.2 Setting Monitoring Parameters for a UPS2000-H (over SNMP)
Before connecting UPS2000-H to NetEco, you should set the IP address on the
UPS2000-H, add user and set permissions on the WebUI of UPS2000.
Prerequisites
●
You have obtained the IP address, subnet mask, and default gateway
information planned for the UPS2000.
●
The UPS2000 is powered on.
Context
●
UPS WebUIs may vary slightly depending on the UPS software version.
Perform operations based on the actual WebUI.
●
Connecting the UPS2000 to the NetEco in DES and MD5 protocols poses
potential risks. Therefore, exercise caution when deciding to do so.
Procedure
Step 1 Set SNMP card parameters on the app.
1. Log in to the app. For details, see
2. On the main screen, tap Settings.
3. Tap Optional card settings and set the SNMP card IP address, SNMP card
subnet mask, and SNMP card gateway.
Step 2 Log in to the UPS2000-H WebUI.
1. On the PC with an IP address in the same network segment as the UPS2000-
H, type https://IP address of the UPS2000-H in the address box of a browser
and press Enter.
2. Enter the user name and password for logging in to the UPS2000-H and click
Login.
NO TE
The preset user name and password for the UPS2000-H are admin and Changeme,
respectively. To ensure access security, change the password after first login.
3. Set user permissions by referring to
based on the site
requirements.
Step 3 Add a user and set user permissions on the WebUI (WebUI 1).
1. Choose System Settings > SNMP Settings.
2. In the SNMP area, set SNMP Version to SNMPv3 and SNMP Port to 161,
and click Submit.
3. In the SNMPv3 area, click Add.
4. In the displayed SNMPv3 dialog box, set SNMPv3 parameters, and click
Confirm.
–
You are advised to set MD5/SHA password and DES/AES password to
different values.
–
MD5 is an insecure protocol. SHA is recommended. DES is an insecure
protocol. AES is recommended.