Step 6 Select the device to be added and drag its icon to the management domain.
NO TE
To delete a device, click the device and choose Delete under
.
Step 7 Click the device. In the device parameter area on the right, set device parameters
according to the following table.
Table 6-50 Modbus-RTU device parameter description
Parameter
Description
Managed Object
Name
Device name
IP
IP address of the collector to which the device is connected
Port
Port through which the device connects to the collector
For details about the ports on the ECC800-Pro collector, see
6.5.1.4 Setting RS485 Parameters for the ECC800-Pro
.
Device Address
Address set on the device
Step 8 Click
on the toolbar to save the device information.
Step 9 Click Connection test to start the connection test.
----End
6.5.9 Adding an rPDU
6.5.9.1 Setting Monitoring Parameters for HPXPDU2000-16-3PH-24-6-M1
Prerequisites
●
You have obtained the device address planned for the PDU2000.
●
The PDU2000 is connected to the collector, and digits are displayed on the
LCD.
●
You have obtained the collector IP address and login user name and
password.
●
A PC with an IP address in the same network segment as the collector has
been prepared and connected to the collector over a switch.
Context
Before connecting the PDU2000 to the NetEco, set its device address and then
modify the port parameters for the collector connecting to the PDU2000 to ensure
that the values of BaudRate, DataBit, StopBit, and Parity on it are consistent
with those for the collector port.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center)
6 Adding Devices
Issue 02 (2021-05-12)
Copyright © Huawei Technologies Co., Ltd.
272