2 Site Requirements
Issue 03 (2020-06-09)
Copyright © Huawei Technologies Co., Ltd.
8
Prepare traps for pre-fab. module drainpipes.
The ends of the drainpipes should be connected to the utility drainpipes.
Figure 2-5
Requirements for wrapping the electric heating belt
The electric heating belt needs to be wrapped around the drainpipe and water refill pipe
evenly during onsite installation.
Wrap the electric heating belt before wrapping the thermal insulation foam. Ensure that the
thermal insulation foam covers the electric heating belt. The thermal insulation foam must
be able to withstand a temperature higher than 200°C.
2.6 External Environment Requirements
Temperature:
−
Normal temperature working condition: –20°C to +55°C for advanced
configuration; –20°C to +45°C for standard configuration and 208 V scenarios
−
Low temperature working condition: –40°C to +45°C for advanced configuration
Relative humidity: 5%–95% RH
Solar radiation: ≤ 1120 W/m
2