Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
- 52 -
HD3N Series User Manual V1.1
Ref. code
Function Description
Setting Range [Default]
F00.22
Dormancy wake up time
0.0 - 6000.0 [1.0s]
F00.24
Dormancy delay time
0.0 - 6000.0 [1.0s]
F00.25
Dormancy frequency
0.00 - upper limit frequency
[0.00Hz]
F00.21 - F00.25 is used for dormancy and wake up.
•
If HD3N is in dormant status and receive run command, and setting frequency ≥ F00.25, when F00.22
(dormancy wake up time) is finished, HD3N wakes up from dormancy status and starts running;
•
During running, and setting frequency < F00.25, when F00.24 (dormancy delay time) is finished, HD3N
enters dormancy status (Run indicator is lighting, and LED is flashing) and stop running.
F00.26
Action selection of HD3N at zero-speed
000 - 332 [111]
Unit: Action selection of zero-speed under V/f
control
•
0: Do not process.
•
1: HD3N does not output.
•
2: HD3N runs at DC brake.
Ten: Action selection of zero-speed under open
loop vector control
Hundred: Action selection of zero-speed under
torque control
•
0: Do not process.
•
1: HD3N does nto output.
•
2: HD3N runs at DC brake.
•
3: HD3N runs at pre-excitation.
F00.27
Command source binding frequency source
000 - ddd [000]
Valid only for main frequency. When command source is bound to frequency source, frequnecy source set
by F00.10 will be invalid during this binding.
Unit: keypad binds to frequency source
Ten: Terminal binds to frequency source
Hundred: SCI binds to frequency source
•
0: No binding.
•
1: Keypad digital setting.
•
2: Terminal digital setting.
•
3: SCI setting.
•
5: Terminal pulse setting.
•
7: AI1 setting.
•
8: AI2 setting.
•
B: Potentionmeter setting.
•
Valid when LED keypad adopted only.
•
C: PID setting.
•
D: Multi-speed setting.
F00.28
Function of STOP button
0,1 [0]
0: Valid in keypad control mode only.
1: Valid in all control modes.