Shenzhen Hpmont Technology Co., Ltd.
Appendix A Parameters
HD3N Series User Manual V1.1
- 117 -
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
1: Can jog the start and stop
function
Tens:
0: Terminal jog is not preferred
1: Terminal jog is preferred
F02.20
Pre-excitation time
0.00 - 0.50s
0.50s
0.01s
×
F02.21
End selection of DWELL
frequency in stop
0: Time (F02.15)
1: Terminals (88 function)
0
1
×
F03: Acc. / Dec. Parameter (on pages 57 - 58)
F03.00
Acc. / Dec. modes
selection
Unit: Acc. / Dec. modes selection
0: Linear Acc. / Dec.
1: S curve Acc. / Dec.
Ten: Reference frequency for Acc. /
Dec. time
0: Max frequency (F00.06)
1: Setting frequency
00
1
○
F03.01
Acc time 1
0.0 - 6000.0s
7.5 - 15kW
inverter:
10.0s
18.5kW
inverter:
30.0s
0.1s
○
F03.02
Dec time 1
0.0 - 6000.0s
0.1s
○
F03.03
Acc time 2
0.0 - 6000.0s
0.1s
○
F03.04
Dec time 2
0.0 - 6000.0s
0.1s
○
F03.05
Acc time 3
0.0 - 6000.0s
0.1s
○
F03.06
Dec time 3
0.0 - 6000.0s
0.1s
○
F03.07
Acc time 4
0.0 - 6000.0s
0.1s
○
F03.08
Dec time 4
0.0 - 6000.0s
0.1s
○
F03.09
Switching frequency of
acc time 1 and 2
0.00 - upper limit frequency
0.00Hz
0.01Hz
×
F03.10
Switching frequency of
dec time 2 and 1
0.00 - upper limit frequency
0.00Hz
0.01Hz
×
F03.11
Characteristic time of S
curve at beginning of acc
0.00 - 2.50s
0.20s
0.01s
○
F03.12
Characteristic time of S
curve at end of acc
0.00 - 2.50s
0.20s
0.01s
○
F03.13
haracteristic time of S
curve at beginning of dec
0.00 - 2.50s
0.20s
0.01s
○
F03.14
Characteristic time of S
curve at end of dec
0.00 - 2.50s
0.20s
0.01s
○
F03.15
Jog acc time
0.1 - 6000.0s
6.0s
0.1s
○
F03.16
Jog dec time
0.1 - 6000.0s
6.0s
0.1s
○
F03.17
Dec time for EMR stop
0.1 - 6000.0s
10.0s
0.1s
○
F04: Process PID Control (on pages 58 - 61)
F04.00
Process PID control
selection
0: PID control is disabled
1: PID control is enabled
0
1
×
A