Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD3N Series User Manual V1.1
- 89 -
Ref. code
Function Description
Setting Range [Default]
F19.01
Main/Aux setting calculating
00 - 41 [10]
Define the relationship between final setting
frequency and main/aux frequency.
Switch frequency by No. 54 function of DI terminal
(switching main/aux frequnecy source).
Unit: Main/Aux calculating
0: Main+Aux setting.
1: Main-Aux setting.
Ten: Frequency source selection
0: Main.
1: Main/Aux calculating.
2: Main/Aux switching.
3: Main and Main/Aux calculating switching.
4: Aux and Main/Aux calculating switching.
DI = 54
F19.01setting value
00
10
20
30
40
01
11
21
31
41
0
Main Main+Aux Aux Main+Aux Main+Aux Main Main-Aux Aux Main-Aux Main-Aux
1
Main Main+Aux Main
Main
Aux
Main Main-Aux Main
Main
Aux
F19.02
Aux setting coefficient
0.00 - 9.99 [1.00]
Use F19.02 to calculate gain, then calculate aux frequency by F05.
•
Valid when F19.00 = 4,5,7 - 8.
F19.03
Initial value of digital aux frequency
0.00 - F00.06 [0.00Hz]
Valid when 19.00 = 1,2. F19.03 is initial value for the two aux frequency setting.
F19.04
Digital aux frequency control
00 - 11 [00]
Valid when F19.00 = 1,2.
Unit: Storage selection at power failure
•
0: Do not save aux frequency.
•
1: Save aux frequency.
Ten: Frequency at stop
•
0: Maintain aux frequency at stop.
•
1: Aux frequency resumes to F19.03 at stop.
F19.05
Setting frequency adjustment selection
0 - 2 [1]
F19.06
Setting frequency adjustment coefficient
0.0 - 200.0 [100.0%]
F19.05,F19.06 define the adjustment ways of setting frequency (the frequency that calculated by main and
aux setting frequency is shorted as resultant frequency).
0: Do not adjust.
•
Setting frequency = resultant frequency.
1: Adjust according to max. output frequency (F00.06).
•
Setting frequency = resultant fre F00.06 × (F19.06 – 100%).
2: Adjust according to current frequency.
•
Setting frequency = resultant frequency × F19.06.
Cooling fan (F19.07 - F19.08)
Ref. code
Function Description
Setting Range [Default]
F19.07
Fan control
0 - 2 [0]
F19.08
Fan control delay time
0.0 - 600.0 [60.0s]
Defines the control mode of cooling fan. With overheat protection, the fan runs all the time.
0: Auto stop.
•
The fan runs all the time when HD3N is running. After HD3N stops for the time set by F19.08, the fan
continues running if overheat protection is activated.
1: Immediate stop.
•
The fan runs all the time when HD3N is running and stops when HD3N stops.
2: Runs all the time when power on.
•
The fan runs all the time when HD3N is powered on.
6