Specifications
Environmental specifications
Specification
Value
Temperature range
—
Operating
10°C to 35°C (50°F to 95°F)
Nonoperating
-30°C to 60°C (-22°F to 140°F)
Relative humidity (noncondensing)
—
Operating
Minimum to be the higher (more moisture) of -12°C
(10.4°F) dew point or 8% relative humidity
Maximum to be 24°C (75.2°F) dew point or 90%
relative humidity
Nonoperating
5% to 95%
38.7°C (101.7°F), maximum wet bulb temperature
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 304.8 m (1.8°F per 1000 ft) to 3048 m
(10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). The upper
limit and rate of change might be limited by the type and number of options installed.
For certain approved hardware configurations, the supported system inlet temperature range is extended:
• 5°C to 10°C (41°F to 50°F) and 35°C to 40°C (95°F to 104°F) at sea level with an altitude derating of 1.0°C
per every 175 m (1.8°F per every 574 ft) above 900 m (2953 ft) to a maximum of 3048 m (10,000 ft).
• 40°C to 45°C (104°F to 113°F) at sea level with an altitude derating of 1.0°C per every 125 m (1.8°F per
every 410 ft) above 900 m (2953 ft) to a maximum of 3048 m (10,000 ft).
The approved hardware configurations for this system are listed on the
.
Mechanical specifications
Specification
Value
Height
8.73 cm (3.44 in)
Depth, SFF
67.94 cm (26.75 in)
Depth, LFF
73.02 cm (28.75 in)
Width
44.54 cm (17.54 in)
Weight, SFF minimum
14.9 kg (32.75 lbs)
Weight, SFF maximum
19.5kg (43.00 lbs)
Weight, LFF minimum
17.1 kg (37.75 lbs)
Weight, LFF maximum
24.5 kg (54 lbs)
Specifications
157
Summary of Contents for ProLiant DL388 Gen10
Page 37: ...Customer self repair 37...
Page 38: ...38 Customer self repair...
Page 39: ...Customer self repair 39...
Page 147: ...Option 1 System board Option 2 Controller Option 3 not shown SAS Expander Cabling 147...
Page 149: ...Box 1 to SAS Expander Box 2 to SAS Expander Cabling 149...
Page 151: ...Cable routing Front 8SFF NVMe drive options Box 1 Box 2 Cabling 151...
Page 152: ...Box 3 Cable routing Front 2SFF NVMe drive option for SFF 152 Cabling...