is a single-phase unit that branches out into four single-phase branch circuits. The power strips
mount directly to the rear of the rack frame and plug into the control units.
Each HP Cluster Platform rack has up to four modular PDUs. For Cluster Platform racks with
server blades there may be up to eight modular PDUs in the rack. Each control unit has four
outlet receptacles. However, all four outlet receptacles might not be in use simultaneously because
the total capacity of each PDU cannot exceed 40A for PDU models shipped to the US and Japan
or exceed 32A for international PDU models. For the latest information on the power specifications,
see the HP Modular Power Distribution Units (Zero-U/1U Modular PDUs QuickSpecs, available
from:
http://h18000.www1.hp.com/products/quickspecs/11041_div/11041_div.html
Figure 2-31 Power Distribution Unit Zero-U Mount
1
3
2
4
6
5
7
8
The following list describes the callouts in
Figure 2-31
:
1.
Installation screws and cage nuts secure the PDU to the side of the rack column, adjacent to
the racks's side panel for servicing
2.
The rack's front left column
3.
Main inlet power cable, which is connected to the power supply
4.
Outlet power cables (up to 4) that connect to the power strips (see
Figure 2-33
)
5.
Connector shield, providing support for the outlet power cables
6.
PDU main breaker switch
7.
Individual breaker switches (four)
8.
Direction of view towards the rear of the rack
Note that the orientation and the hardware will be different for a 1U PDU installation. For more
information on how to install both the zero-PDU and 1U PDU control unit, see the HP Modular
Power Distribution Unit Kit Installation Instructions, available from:
http://bizsupport.austin.hp.com/
bc/docs/support/SupportManual/c00258165/c00258165.pdf
56
Platform Core Components
Summary of Contents for Cluster Platform
Page 8: ...8 ...
Page 14: ...14 ...
Page 18: ...18 ...
Page 20: ...20 ...
Page 31: ...Figure 2 6 HP Modular Cooling System Front View 2 5 HP Modular Cooling System 31 ...
Page 62: ...62 ...
Page 70: ...70 ...
Page 72: ...72 ...
Page 76: ...76 ...
Page 82: ...82 ...
Page 87: ...87 ...
Page 88: ... A CPCCO 1F Printed in the US ...