System expansion
BA_sun_power_pack_LiOn_en_V1.05.docx
V1.05 (20/07/2017) 6140203036
49
13.
System expansion
The storage capacity may be enhanced subsequently by connecting individual battery
systems in parallel. Only battery systems of identical capacity can be connected in parallel.
Note:
The age difference (from the date of commissioning) between the individual systems to be
connected in parallel should not exceed 24 months.
HOPPECKE offers an appropriate accessories kit for connecting individual battery systems
in parallel. Parallel operation of multiple battery systems must be done only with the help of
original HOPPECKE accessories. Refer to the documentation supplied for setting up and
connecting the accessories kit.
14.
Disassembly
You need to carry out the following steps to disassemble the battery store system for repair,
replacement or disposal:
1. Switch off the battery inverter.
2. Pull out the connecting plug on the top of the battery store system.
3. Open the cover of the battery store system.
4. Start from the "top left to the bottom right":
5. Disconnect the terminals of the battery stacks (top left plus terminal, top cable to the
BMS, top right minus terminal, bottom left plus terminal, bottom cable to the BMS,
bottom right minus terminal).
6. Loosen the battery stacks from the mounts (loosen 2 Allen screws of 4 mm each)
7. Remove the battery stacks from the housing and pack them safely in the original
packaging.
8. Loosen the housing from the mount (4 mm Allen screw).
9. Lift the housing from the wall.
10. Pack the housing in the delivery packing.