Warning and erorr messages
BA_sun_power_pack_LiOn_en_V1.05.docx
V1.05 (20/07/2017) 6140203036
47
12.
Warning and erorr messages
In case of an active error, the battery management system interrupts the battery charging /
discharging operation (see overview of error messages in Table 3). Note the hints in column
“Remarks / Measure”.
No.
Code
Meaning
Remarks / Measure
1
1
Overvoltage
Maximum cell voltage
BMS prevents further charging.
Battery discharge possible.
2
2
Undervoltage
Minimum cell voltage
BMS prevents discharging.
Battery charging possible.
3
4
Overtemperature
Cell temperature > 60°C: BMS interrupts
battery operation until system has cooled
off.
4
8
Undertemperature
Cell temperature < 0°C: BMS stops
charging.
Check environmental conditions (5° to
45°C).
5
16
Undertemperature
Minimum cell temperature discharging
< -10°C. BMS interrupts battery operation.
Check environmental conditions (5° to
45°C).
6
32
Overtemperature
BMS temperature > 90°C: BMS interrupts
battery operation until temperature is in an
acceptable range.
7
64
Deep discharge
Switch the BMS on by plugging in the
connection cable to the battery system and
apply the charging current.
8 to 13
128, 256,
512, 1024,
8192,
16384
Hardware error
Electronic error
Do not make use of the battery any longer.
Contact HOPPECKE Service, the BMS
must be replaced.
14
32768
Cell error
Do not make use of the battery any longer.
Contact HOPPECKE Service.
15
65536
Contact Service
Contact HOPPECKE Service, the BMS
must be replaced.
Table 3: Error codes
Note: In case of multiple simultaneous errors the error codes will be summed up. Example:
overvoltage (Code 1) and overtemperature (32) => 1 + 32 = 33.