OMNI-408/OMNI-408EU Installation and Setup Guide
2–4
BACKUP BATTERY:
The Red (+) and Black (-) flying leads must be connected to a 12VDC 4-7AH battery to serve as backup
power in the event of AC loss.
A battery test occurs approximately every 4.5 minutes. Low-battery conditions occur at nominal
11VDC. The keypad AC/LB LED and buzzer will pulse slowly when a low-battery condition is detected.
The system reports this condition to the central station if programmed to do so. Battery restoration
occurs within 4.5 minutes, at the NEXT battery test. The buzzer may be silenced by entry of any valid
user code.
NOTE:
For UL installations, use two 4AH batteries connected in parallel.
Auxiliary Device Current Draw Worksheet
DEVICE
CURRENT DRAW
FOR EACH
NUMBER OF
UNITS
TOTAL CURRENT
FOR EACH
OMNI-LCD and OMNI-LCD-US
(Standby/Alarm)
40mA/180mA
XK7LC 65mA
XK108 (Max.)
30mA
OMNI-KP and OMNI-KP-US
(Standby/Alarm)
40mA/70mA
PIR **
Smoke Detector
**
Glassbreak Detector
**
**
**
Total Current or all Devices = (500mA max.)
**If devices such as PIRs, smoke detectors, etc. are used, refer to the specifications for that particular
device's current draw. If the total current draw exceeds 500mA, then use an additional power supply.
NOTE:
For UL installations, do not exceed 180mA.
NFPA, UL, and the California State Fire Marshal require the backup battery to provide power
for 24 hours. The maximum auxiliary power will vary by the ampere/hour rating of the battery
used:
5AH = 95mA; 7AH = 180mA; 8AH = 210mA.
Summary of Contents for OMNI 408
Page 6: ...vi ...
Page 28: ...OMNI 408 OMNI 408EU Installation and Setup Guide 5 4 ...
Page 72: ...OMNI 408 OMNI 408EU Installation and Setup Guide 8 4 ...
Page 98: ...OMNI 408 OMNI 408EU Installation and Setup Guide D 4 ...
Page 100: ...OMNI 408 OMNI 408EU Installation and Setup Guide E 2 ...
Page 103: ......