OMNI-408/OMNI-408EU Installation and Setup Guide
7–8
QUICK FORCED ARMING
- Specifies whether Quick Forced Arming ([#] [2]) is permitted. If chosen,
Quick Forced Arming arms the system bypassing any faulted zones. Openings/Closings report User no.
8 to the CS if enabled.
QUICK ARMING
- Specifies whether Quick Arming ([#] [1]) is permitted. If chosen, Quick Arming
arms the system ONLY if the system is READY. Openings/Closings report User no. 8 to the CS if
enabled.
QUICK BYPASS
- Specifies whether bypassing a zone without a user code is permitted.
QUICK EXIT
- If enabled, this feature allows the user to exit without having to disarm, then arm, the
system. It is activated by pressing the [STAY] key while the system is armed and not in entry delay.
This starts exit time, causes the keypad to beep once, and allows the user to exit without disarming the
system. The system returns to its last armed state after exit time has expired.
Question 07, L4
Rest. Foll. Loop, User On-line, Bell Test from RF Keyfobs, & User 5 Arm
Default = 4
Enter the digit from the table below in Location L4.
NOTE:
The checkmarks highlight which options are selected.
Digit
RESTORE
AFTER BELL
RESTORE
FOLLOWS LOOP
USER ON-LINE
BELL TEST
FROM RF
KEYFOBS
USER 5 ARMS
ONLY
0
9
1
9
2
9
9
3
9
9
4
9
9
5
9
9
6
9
9
9
7
9
9
9
8
9
9
9
9
9
A
9
9
9
B
9
9
9
C
9
9
9
D
9
9
9
E
9
9
9
9
F
9
9
9
9
RESTORE AFTER BELL
- Restores are transmitted after the loop has returned to normal after bell
cutoff, or upon system disarming, regardless of the loop status.
RESTORE FOLLOWS LOOP
- Restores are transmitted immediately upon zone restoral while the
system is armed, or upon system disarm, regardless of the loop status.
Summary of Contents for OMNI 408
Page 6: ...vi ...
Page 28: ...OMNI 408 OMNI 408EU Installation and Setup Guide 5 4 ...
Page 72: ...OMNI 408 OMNI 408EU Installation and Setup Guide 8 4 ...
Page 98: ...OMNI 408 OMNI 408EU Installation and Setup Guide D 4 ...
Page 100: ...OMNI 408 OMNI 408EU Installation and Setup Guide E 2 ...
Page 103: ......