F–1
A P P E N D I X F
Summary of Connections
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
ANTENNA 2
P2
P3
RF RECEIVER
DIRECT PLUG-IN
(Wireless Zones)
SYSTEM DEFAULT
RESET JUMPERS
JP1 JP2
To re-load factory default values, remove all power
(AC & DC). Short JP1 to JP2. With short still applied
er-apply power (AC then DC), wait 5 seconds, then
remove short with power still applied.
FUSES:
F1 = Amp. Power, 1 Amp
F2 = Bell Power, 3 Amps
F3 = Battery, 4 Amps
This fuse is
NOT replaceable.
(SEE NOTE 11)
P1
TRIGGER
OUTPUTS
(SEE NOTE 3)
VBELL
T2
T1
BLACK
RED
CLK
DATA
GND
+ 5V
NOTE
Zones 1-4 can be
handwired or wireless.
Zones 5-8 can only be wireless.
F2
F3 F1
TELCO
HOME
RJ31X OR
CA31A JACK
BLACK
YELLOW
GREEN
RED
TRANSFORMER
16.5VAC, 25VA
(Connect to 24 HR.
120VAC, 60 Hz Outlet
SEE NOTE 6)
GROUND LUG
(SEE NOTE 3)
2.2K
ZONE
4
2.2K
ZONE
3
2.2K
ZONE
2
2.2K
ZONE
1
SELF-
CONTAINED
SIREN
-
+
OR
+
AUX POWER (8 +) & (5 -)
12VDC Reg., 500mA Max.
(SEE NOTE 1)
SMOKE POWER (8 +) & (7 -)
SIREN SUPERVISION
JP3
BELL OR SELF-CONTAINED SIREN
(LEFT)
SIREN DRIVER
(RIGHT)
JP3
1 2 3
1 2 3
12V, 4-6AH
BATTERY
MODEL 1240A
(SEE NOTE 8)
RECEIVER
INTERNAL
CONNECTIONS
WARNING
To prevent risk from
electrical shock,
de-energize the system
control unit and disconnect
the telephone lines before
servicing this unit.
(SEE NOTE 14)
ONMI408-SOC-V2
ANTENNA 1
+
_
8
9
14
15
18
16
17
10
11
12
13
5
6
7
2
3
4
1
BELL
FIRE & BURGLARY
ALARM OUTPUT
(11.5 - 13.1VDC,
1A max)
(SEE NOTE 2)
+
+
+
+
BYPASS
INSTANT
CODE
READY
ARMED
STAY
5
6
4
8
9
7
0
2
3
1
#
THIS UNIT INCLUDES AN ALARM VERIFICATION
FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL UNIT
PLUS SMOKE DETECTOR) SHALL NOT EXCEED 60
SECONDS. NO OTHER INITIATING DEVICES SHALL
BE CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING
JURISDICTION.
UL INSTALLATIONS REQUIRE LISTED END-OF-LINE
SERVICE. USE RESISTOR FROM EOL22 KIT.
LOOK FOR LISTING MARK ON ITEM
WARNING
ALL CONTROL PANEL WIRING SHOULD BE COM-
PLETED PRIOR TO APPLYING POWER TO AVOID
POSSIBLE HARM TO CIRCUITS DUE TO ELECTRO-
STATIC DISCHARGE
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARD
72, CHAPTER 2(NATIONAL FIRE PROTECTION
ASSOC., BATTERY-MARCH PARK,QUINCY,MA
02269)PRINTED INFORMATION DESCRIBING
PROPER INSTALLATION,OPERATION TESTING,
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARM-
FUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING
INTERFERENCE THAT MAY CAUSE UNDESIRED
OPERATION.
IMPORTANT
USE WITH XK108 OR
OMNI-LCD, OMNI-LCD-US,
XK7LC, OMNI-KP AND
OMNI-KP-US
Summary of Connections
Summary of Contents for OMNI 408
Page 6: ...vi ...
Page 28: ...OMNI 408 OMNI 408EU Installation and Setup Guide 5 4 ...
Page 72: ...OMNI 408 OMNI 408EU Installation and Setup Guide 8 4 ...
Page 98: ...OMNI 408 OMNI 408EU Installation and Setup Guide D 4 ...
Page 100: ...OMNI 408 OMNI 408EU Installation and Setup Guide E 2 ...
Page 103: ......