Operation
63
6.4.2
"Main" register (main display)
An overview of the most important measurements is presented in the
"Main" register. Depending on settings, the contents (see Chapter 6.4.6.5)
may vary.
Display
Description
Unit
Access
Address
V1
Main counter input 1
m
3
PL
1:200
V2
Main counter input 2
m
3
PL
2:200
V3
Main counter input 3
m
3
PL
3:200
V4
Main counter input 4
m
3
PL
4:200
Time
Time on the device
-
PL
1:400
6.4.2.1 V1 to V4
– Main counter of the respective input
This meter counts the incoming pulses and converts these into a volume
via the cp value set. To control the measurements, the V1 can be kept at
the same level as the meter at this input when putting the device into
operation (
chapter 5.3.1 "Configuration of measurement parameters").
6.4.2.2 Vo1 and Vo2 - Original meter readings of the respective inputs
This meter is only available in encoder mode. It shows the original meter
reading of the respective meter, which was transmitted by the encoder.
This means that Vo is always automatically on the state of the meter and
cannot be changed.
6.4.2.3 Time
– Date and time
The time displayed is updated every 900 seconds in battery operation and
naturally, the update takes place immediately when switching on the
display. In mains operation and during communication, updating takes
place every two seconds.
Summary of Contents for DL230
Page 6: ......
Page 98: ...98 Appendix 9 3 EC Declaration of Conformity ...
Page 99: ...Appendix 99 9 4 ATEX Type Examination Certificate 9 4 1 Associated apparatus for Zone 0 1 ...
Page 100: ...100 Appendix ...
Page 101: ...Appendix 101 ...
Page 102: ...102 Appendix ...
Page 103: ...Appendix 103 ...
Page 104: ...104 Appendix ...