24
Technical data
3.5.2
Encoder inputs
An encoder can only be connected to inputs 1 and 2 (termi-
nals DE1 and DE2).
Data
Value
Unit
Encoder protocol
Namur, SCR, SCR+
-
Cable length
max. 30
m
3.6 Digital outputs
Both DA1 and DA2 digital outputs can be configured as low frequency
pulse or signal outputs.
3.6.1
Nominal data
Data
Value
Unit
Maximum switching voltage
30
V DC
Maximum switching current
100
mA DC
Maximum voltage drop
1
V
Maximum residual current
0.001
mA
Pulse duration
min.
125
ms
Pause duration
min.
125
ms
Output frequency
max.
4
Hz
cable cross-section
0,3 … 2,5
mm
2