42
Assembly, Connection and Putting into Operation
An electrically-insulated output only requires electricity if the
output is active (switched-on). You can therefore minimize the
negative influence of an electrically-insulated output on the
battery life by setting the pulse duration to the lowest possible
value when using it as a pulse output.
The configuration software "enSuite" is suitable for this pur-
pose.
The electrical insulation of the outputs is not an approved
electrical isolation in accordance with ATEX. An approved Ex-
isolator is required when using the device as associated
apparatus in Ex zone 0 or 1.
In order to activate the electrical insulation of an output, move the switch
lever behind the corresponding output terminal away from the terminal:
Ill.: 11
Switch for electrical isolation
Output DA2 is electrically isolated
(the slider on the switch is up)
Output DA1 is not electrically isolated
(the slider on the switch is down)