Section 1: General Information
1-5
Backup Battery: 6V, 3.1AH, Honeywell part number K14139, (included)
Expected Battery Life: 5 Years (approx.)
Fault Relay Output: Open collector, 12VDC, .25W max.
Positive Trigger Level: 6V or greater = positive trigger. (4V or less = restore.)
Negative Trigger Level: 4V or less = negative trigger. (6V or greater = restore.)
RF
Transceiver Type: Quad-Band GSM/GPRS Class 10
Modulation: GMSK
Antenna: Internal GSM quad-band antenna 1.3 dBi gain
Band
Transmission
Frequency
(MHz)
Transmit
Power
(dBm)
Receive
Frequency
(MHz)
Receive
Sensitivity
(dBm)
Number
of
Channels
Channel
Spacing
(MHz)
Duplex
Separation
(kHz)
GSM 850
824-849 33
869-894
-107
124
200 45
GSM 900
890-915 33
935-960
-107
124
200 45
GSM 1800
1710-1785 30
1805-1880
-106
374
200 95
GSM 1900
1850-1910 30
1930-1990
-105.5
299
200 80
Ethernet
Network Standard: IEEE 802.3u compliant
Data Rate: 10Base-T / 100Base-T with auto detect
Ethernet Cable: Cat. 5 (min), MDI/MDI-X auto crossover
Environmental
Operating temperature: -20ºC to +55ºC, for UL/ULC installations 0ºC to +49ºC
Storage temperature: -40º to +70ºC
Humidity: 0 to 95% relative humidity, non-condensing
for UL installations 0% to 85%; for ULC installations 0% to 93%
Altitude: to 10,000 ft. operating, to 40,000 ft. storage
Compatibility
For a list of control panels that are compatible with various features of this device, go to:
http://www.security.honeywell.com/hsc/resources/MyWebTech
.
After logging on, select the applicable communication product, and then select “Compatibility
Chart” under Essential Docs.
For UL and ULC Fire and Burglary installations, compatible control panels are:
Vista-32FB
FA1670C
Vista-128FBP
FA1700C
Vista-250FBP
For UL and ULC Fire and Burglary installations, compatible receivers are:
MX8000 (UL – can be used for secondary reporting in ECP mode and Zone Trigeer mode.
Shall be used for opening and closing ring back with the control panel dialer)
7810iR-ENT (UL – must be the primary alarm receiver.)
Ademco 685
Summary of Contents for AlarmNet IGSMV
Page 2: ......
Page 20: ...IGSMV IGSMVCN Installation and Setup Guide 2 10 ...
Page 46: ...IGSMV IGSMVCN Installation and Setup Guide 4 4 ...
Page 54: ...IGSMV IGSMVCN Installation and Setup Guide A 2 ...
Page 56: ...IGSMV IGSMVCN Installation and Setup Guide B 2 ...
Page 58: ...IGSMV IGSMVCN Installation and Setup Guide C 2 ...
Page 60: ...IGSMV IGSMVCN Installation and Setup Guide D 2 ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...