Section 3: Programming the IGSMV
3-13
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
13
Primary Sub ID
(????)
[0001-
9999]
Enter the 4-digit subscriber account number,
0001-9999 (decimal).
14
Device Address
(12)_
[01-15]
The IGSMV communicates with the control
panel as a 4204 relay module. Enter the
appropriate address. For VISTA-10P, and
FA130CP Series control panels, this must be
address 12. For other controls, see the control
panel’s Installation and Setup Guide.
NOTES:
1. The 4204 protocol limits address range to
01-15. If using 2-4204 mode, the IGSMV
assigns the second 4204 to the next higher
device address (e.g., if entering address 12
for the first 4204, then address 13 is
automatically assigned to the second 4204
module). Program the control panel
accordingly.
2. The device address(es) must be unique from
the "Keypad Address" entered in Prompt 17
and any other address used on the control
panel.
UL / ULC
Remote access has not been evaluated by UL or ULC.
15
RemoteAccess
Y/N (N)_
[Y], [N]
Press [Y] to allow the end user to access their
system via a website. Availability of this
service is controlled by the dealer via the web-
based programming tool on the AlarmNet
Direct website.
16
Direct Wire Y/N
(N)_
[Y], [N]
Applies
only
to VISTA-128BP/250BP and FBP
Series control panels, and FA1660C and 1700C
Series control panels.
Enables Direct Wire Downloading over IP.
If [N], and if Prompt 15: "Remote Access" is
disabled, skip to Prompt 18: "Supervision."
17
Keypad Address
(28)_
[01-30]
This address must be programmed if using
either the Remote Access feature or Direct Wire
downloading. Enter the appropriate device
address.
NOTES:
1. This address must also be programmed as an
alpha keypad in the control panel or an AUI
(Advanced User Interface) type device, if a full
enhanced graphic interface to the system is
desired and the control panel supports it. DO
NOT connect an actual keypad (or any other
device) assigned to this address.
2. This address must be unique from the "Device
Address" entered in Prompt 14, and cannot
equal that device address plus 1 (one) if using
2-4204 mode.
Summary of Contents for AlarmNet IGSMV
Page 2: ......
Page 20: ...IGSMV IGSMVCN Installation and Setup Guide 2 10 ...
Page 46: ...IGSMV IGSMVCN Installation and Setup Guide 4 4 ...
Page 54: ...IGSMV IGSMVCN Installation and Setup Guide A 2 ...
Page 56: ...IGSMV IGSMVCN Installation and Setup Guide B 2 ...
Page 58: ...IGSMV IGSMVCN Installation and Setup Guide C 2 ...
Page 60: ...IGSMV IGSMVCN Installation and Setup Guide D 2 ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...