Section 3: Programming the IGSMV
3-7
PROMPTS
ENTRY
OPTIONS
DESCRIPTION
29
Notify Panel Of_
(Neither Fault)
[Neither
fault]
[Both IP and
GSM Faults]
If "Both IP and GSM Fault" is selected, the device will
only notify the control panel if both communication
paths fail, but will always send notification of either
failure to the central station.
NOTE:
The fault relay output (if programmed) will be
triggered only if "Both IP and GSM Faults" is selected.
Press the [space] key to scroll through choices.
UL/ULC:
Must be set to "Both IP and GSM Faults".
30
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault. For conditions that trip
the fault relay refer to
Module Supervision Features
in
Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring for
Module Fault Relay
in Section 2.
UL/ULC:
Must be set to "Y."
31
Pwr Loss Rpt Y/N
(Y)_
[Y], [N]
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A restore
report is sent within 1-3 hours after power is restored.
UL/ULC Standard Installations
(using transformer
and battery)
:
Must be set to "Y".
ULC Commercial Fire & Burglary Installations
(powered from the control panel)
:
Must be set to "N."
32
Low Bat Rpt Y/N
(Y)_
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low battery restore is
automatically sent when the low battery condition
clears.
UL/ULC Standard Installations
(using transformer
and battery)
:
Must be set to "Y".
ULC Commercial Fire & Burglary Installations
(powered from the control panel)
:
Must be set to "N."
33
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report when the module detects a
tamper condition. A tamper restore is automatically
sent when the tamper condition clears.
UL/ULC:
Must be set to "Y."
Important Information Regarding Zone Input Options
ECP mode
supports two optional hardwire zone input triggers by making connections to the module’s zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
(V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
(V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
(EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
UL Installations
, V+ is to be set as inverted and V– as non-inverted.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting (NOT for UL installa-
tions), which allows time for the user to abort false alarms.
NOTE:
Optional hardwire zones report in ADEMCO High-Speed format.
34
Enable Zn6 Y/N
(N)_
[Y], [N]
Enables alarm reporting for zone 6.
If [N], skip to Prompt 39: "Enable Zn7."
Summary of Contents for AlarmNet IGSMV
Page 2: ......
Page 20: ...IGSMV IGSMVCN Installation and Setup Guide 2 10 ...
Page 46: ...IGSMV IGSMVCN Installation and Setup Guide 4 4 ...
Page 54: ...IGSMV IGSMVCN Installation and Setup Guide A 2 ...
Page 56: ...IGSMV IGSMVCN Installation and Setup Guide B 2 ...
Page 58: ...IGSMV IGSMVCN Installation and Setup Guide C 2 ...
Page 60: ...IGSMV IGSMVCN Installation and Setup Guide D 2 ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...