IGSMV
/
IGSMVCN Installation and Setup Guide
3-6
PROMPTS
ENTRY
OPTIONS
DESCRIPTION
address.
2. This address must be unique from the "Device
Address" entered in Prompt 19.
23
Supervision
(24 Hours)_
30 Day
24 Hrs
None
Additional options
for CN only
1 Hr
CN UL Line
Lvl 3
(3 Min)
CN UL Line
Lvl 4
(90 Sec)
CN UL Line
Lvl 5
(75 Sec)
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. (If the supervision period is changed after
registration, you must re-register the module.)
Press the [space] key to scroll through choices.
UL:
A loss of communications is treated as an Alarm
condition.
ULC
: Must be set to" CN UL Line Lvl 3" for ULC-
S304 Active Level 3 or ULC-S559 Active Fire
installations. All other commercial applications must
be set to "24 Hrs".
24
GSM Rollover Y/N
(N)_
[Y] , [N]
If enabled, all messages (including AlarmNet network
supervisory messages) are sent over the GSM network
in the event of an Internet failure.
If disabled, all messages (except AlarmNet network
supervisory messages) are sent automatically over the
GSM network in the event of an Internet failure.
UL/ULC
: Must be set to "Y" if 24 hours is selected in
Prompt: 23: Supervision. Must be set to "N" for ULC-
S304 Active Level 3 or ULC-S559 Active Fire
installations where CN UL Line Lvl 3 is selected.
IMPORTANT WARNING:
If set to "Y", AND Prompt
23: Supervision is set to occur less than every 24
hours, this can result in data overage charges on your
monthly bill.
25
GSM 24Hr Tst Y/N
(N)_
[Y], [N]
If enabled a message is sent every 24 hrs over GSM to
verify proper operation. If it fails, a Periodic Comm
Test Failure message will be sent over Ethernet.
UL/ULC:
Must be set to "Y".
26
Old Alarm Time
10 Minutes_
10 Minutes
15 Minutes
30 Minutes
1 Hour
2 Hours
4 Hours
8 Hours
12 Hours
24 Hours
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
UL/ULC:
Must be 10 minutes.
27
IP Flt Time
(60 mins)_
[01-99]
In the event there is a loss of contact with the network
over the Ethernet connection, enter the time delay (in
minutes) before the IGSMV notifies the central
station. IP failure will always be sent to the central
station as Primary Communication Path Failure.
UL/ULC:
Must be one (01) minute.
28
GSM Flt Time
(60 mins)_
[01-99]
In the event the module detects a communication path
failure, enter the time delay (in minutes) before the
IGSMV notifies the central station. A GSM failure
will always be sent to the central station as Secondary
Communication Path Failure.
UL/ULC:
Must be one (01) minute.
Summary of Contents for AlarmNet IGSMV
Page 2: ......
Page 20: ...IGSMV IGSMVCN Installation and Setup Guide 2 10 ...
Page 46: ...IGSMV IGSMVCN Installation and Setup Guide 4 4 ...
Page 54: ...IGSMV IGSMVCN Installation and Setup Guide A 2 ...
Page 56: ...IGSMV IGSMVCN Installation and Setup Guide B 2 ...
Page 58: ...IGSMV IGSMVCN Installation and Setup Guide C 2 ...
Page 60: ...IGSMV IGSMVCN Installation and Setup Guide D 2 ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...