Section 3: Programming the IGSMV
3-15
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
23
GSM Flt Time
(60 mins)_
[01-99]
In the event the module detects a communica-
tion path failure, enter the time delay (in
minutes) before the IGSMV notifies the central
station. A GSM failure will always be sent to
the central station as Secondary
Communication Path Failure.
UL/ULC:
Must be one (01) minute.
24
Notify Panel Of_
(Neither Fault)_
[Neither
fault]
[Both IP
and GSM
Faults]
If "Both IP and GSM Fault" is selected, the
device will only notify the control panel if both
communication paths fail, but will always send
notification of either failure to the central
station.
NOTE:
The fault relay output (if
programmed) will be triggered only if "Both IP
and GSM Faults" is selected.
Press the [space] key to scroll through choices.
UL/ULC:
Must be set to "Both IP and GSM
Faults".
25
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault.
For conditions that trip the fault relay refer to
Module Supervision Features
in Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring for
Module Fault Relay
in Section 2.
UL/ULC:
Must be set to "Y".
26
Pwr Loss Rpt
Y/N (Y)_
[Y], [N]
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after
power is restored.
UL/ULC Standard Installations
(using
transformer and battery)
:
Must be set to "Y".
ULC Commercial Fire & Burglary
Installations
(powered from the control panel)
:
Must be set to "N."
27
Low Bat Rpt Y/N
(Y)_
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery
condition clears.
UL/ULC Standard Installations
(using
transformer and battery)
:
Must be set to "Y".
ULC Commercial Fire & Burglary
Installations
(powered from the control panel)
:
Must be set to "N."
28
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report when the module detects
a tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
UL/ULC:
Must be set to "Y".
29
Lynx Panic Y/N
(N)_
[Y], [N]
Applies only if used with a Lynx, LynxR or
LynxR-EN control LRR trigger connected to the
module's zone terminal.
Reports a Panic alarm on zone 3 when the
module detects a single pulse on zone 1.
No restores are generated for a Panic alarm.
UL/ULC:
The LYNX controls have not been
Summary of Contents for AlarmNet IGSMV
Page 2: ......
Page 20: ...IGSMV IGSMVCN Installation and Setup Guide 2 10 ...
Page 46: ...IGSMV IGSMVCN Installation and Setup Guide 4 4 ...
Page 54: ...IGSMV IGSMVCN Installation and Setup Guide A 2 ...
Page 56: ...IGSMV IGSMVCN Installation and Setup Guide B 2 ...
Page 58: ...IGSMV IGSMVCN Installation and Setup Guide C 2 ...
Page 60: ...IGSMV IGSMVCN Installation and Setup Guide D 2 ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...