Section 2: Mounting and Wiring
2-7
Wiring for Module Fault Relay
You may wire and program the module's fault output trigger for fail-safe mode (see the
question "FLT REL ON Y/N").
To sense a module fault at the control panel, make connections as shown in
Figure 2-6
,
including the proper EOL resistor required by the control..
UL / ULC
For Commercial Burglary, a 24 hour zone (supervisory) must be assigned on the
control panel, with the communication module's fault relay wired to that zone.
iGSMBR-011-V0
12V AUX
GND
ZONE IN (+)
2K EOL
RESISTOR
CONTROL PANEL
GND
ECP (+) VOLTAGE INPUT
2
1
4
3
TB1
TRANSFORMER
AC INPUT 2
AC INPUT 1
RAD FLT
11
COMMUNICATIONS
MODULE
J1
BATTERY
Figure 2-6. Wiring the IGSMV Fault Relay to a Control Panel Zone for Normally Closed Fault
Ethernet Connections
UL
For UL installations, the Cat. 5 Ethernet connection between the IGSMV and the router
cannot exceed 12 feet with both the IGSMV and the router located within the same room.
Use a Listed cable/DSL router suited for the application.
Connect one end of the Ethernet cable (Category 5) to the IGSMV’s RJ45 Ethernet connector
and the other end to the cable/DSL router as shown in the figure below.
TO ROUTER
RJ45
(FOR INTERNET
CONNECTION)
7720P
PROGRAM
CONNECTOR
J1
BATTERY
CONNECTOR
RSSI
M0
M1
GPRS
IBS
iGSMBR-012-V0
Figure 2-7. Ethernet Connections
Summary of Contents for AlarmNet IGSMV
Page 2: ......
Page 20: ...IGSMV IGSMVCN Installation and Setup Guide 2 10 ...
Page 46: ...IGSMV IGSMVCN Installation and Setup Guide 4 4 ...
Page 54: ...IGSMV IGSMVCN Installation and Setup Guide A 2 ...
Page 56: ...IGSMV IGSMVCN Installation and Setup Guide B 2 ...
Page 58: ...IGSMV IGSMVCN Installation and Setup Guide C 2 ...
Page 60: ...IGSMV IGSMVCN Installation and Setup Guide D 2 ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...