72
Section V.
Parameter Function Table
It is used to set digital input terminal effective mode.
High level valid
:
Connection between COM and corresponding DI is valid,disconnection invalid.
Low level valid
:
Connection between COM and corresponding DI is invalid,disconnection valid.
5.7
Output terminal
:
P5.00-P5.22
HV590 series inverter provides two multifunctional analog terminal output selections,two
multifunctional relay output terminal, oneDO terminal (can be used as high speed pulse output
terminal as well as open collector switching output). If the above output terminals can not meet
the field application, users should choose optional multi-function input/output expansion card.
Output terminals of multi-fuction input/output expansion card contain 1 multi-function analog
output terminal(DO2), 1 multi-function relay output terminal (relay 2) , 1 multi-function digital
output terminal(DO2).
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limite
P5.00
Y terminal output mode
selection
Pulse output(Y1P)
0
0
☆
Switch output(Y1R)
1
Y1 is programmable multiplex terminal, which can be used as high speed pulse output terminal (Y1P)
or open collector switching output terminal (Y1R).
When P5.00 is set to 0, maximum output frequency can reach 10kHz , please refer to P5.06 for related
description.
P5.01
Y1Rselection (open
collector output terminal)
0-40
0
☆
P5.02
Relay output selection
(TA1.TB1.TC1)
0-40
2
☆
P5.03
Expansion card relay output
selection(TA2.TB2.TC2)
0-40
2
☆
P5.04
DO1 output selection(open
collector output terminal)
0-40
1
☆
P5.05
Expansion card DO2 output
selection
0-40
1
☆
The above 5 function codes are used to select 5 digital output function. TA1.TB1.TC1 and
TA2.TB2.TC2 are control board and expansion card relay respectively.
Function selections are as follows
:
Set
value
Function
Description
0
No output
The output terminals have no function
1
Inverter in operation
When the inverter is running, ON signal is output.
2
Output fault(Stop fault)
When inverter fault happens and stops due to the fault ,
ON signal is output