Section IV.
Keyboard Operation
27
3.2
Mounting hole dimension
3.2.1
Braking unit & Braking resistance
When customers choose the type with braking,there will be braking unit inside the
inverter,maximum braking torque is 50%.Please refer to the table below and choose the matched
braking resistance separately.
Shape DIM
Braking
unit
Braking unit
Braking moment %
Braking
Quanti
ty
HV590
−R40G1/G2
Standard
built
-
in
100W
300
Ω
1
220
HV590
−R75G1/G2
120W
200
Ω
1
125
HV590
−1R5G1/G2
300W
100
Ω
1
125
HV590−2R2G1/G2
300W
70
Ω
1
120
HV590
−R75G3
100W
300
Ω
1
130
HV590
−1R5G3
200W
3
00Ω
1
125
HV590
−2R2G3
200W
20
0Ω
1
135
HV590
−3R7G3
400W
150Ω
1
135
HV590
−5R5G3
500W
100Ω
1
135
HV590
−7R5G3
800W
75Ω
1
130
HV590
−011G3
1040W
5
0Ω
1
135
HV590
−015G3
1560W
40
Ω
1
125
HV590
−018G3
4800W
32Ω
1
125
HV590
−022G3
4800W
27.2Ω
1
125
HV590
−030G3
outlay
6000W
20Ω
1
125
HV590
−037G3
9600W
16Ω
1
125
HV590
−045G3
9600W
13.6Ω
1
125
HV590
−055G3
6000W
20Ω
2
135
HV590
−075G3
9600W
13.6Ω
2
145
Table
:
3-2.1
If you need accessories in the table,please declare in order.
For larger built-in braking torque,please use the HNC braking unit.do ou can refer to HNC
braking unit manual for details.
Other large power models do not contain a built-in braking.If large power model need to be
equipped with braking function,please choose HNC braking unit.
External DC reactor installation
:
For HV590 series inverter, external DC reactor can be ordered according to your
needs.When installation,you should tear down copper platoon between DC+1 and DC+2 of
inverter main circuit.And then add reactor between DC+1 and DC+2,wiring between reactor
terminals and inverter terminals DC+1 and DC+2 have no polarity. After installation of dc
reactor,short circuit copper platoon between DC+1 and DC+2 is no more used.