Figure 5.10 shows typical setup cases.
P4.18
AI curve 2 minimum input
0.00V~P4.20
0.00V
☆
P4.19
AI curve 2 minimum input
corresponding setup
-100.00%~100.0%
0.0%
☆
P4.20
AI curve 2 maximum input
P4.18~10.00V
10.00V
☆
P4.21
AI curve 2 maximum input
corresponding setup
-100.00%~100.0%
100.0%
☆
P4.22
AI2 filter time
0.00s~10.00s
0.10s
☆
For function and usage of curve 2, please refer to description of curve 1.
P4.23
AI curve 3 minimum input
-10.00V~P4.25
-10V
☆
P4.24
AI curve 3 minimum input
corresponding setup
-100.00%~100.0%
0.0%
☆
P4.25
AI curve3 maximum input
P4.23~10.00V
8.60V
☆
P4.26
AI curve 3 maximum input
corresponding setup
-100.00%~100.0%
100.0%
☆
P4.27
AI3filter time
0.00s~10.00s
0.10s
☆
For function and usage of curve 3, please refer to description of curve 1.
P4.28
PULSE minimum input
0.00kHz~P4.30
0.00kHz
☆
P4.29
PULSE minimum input
corresponding setup
-100.00%~100.0%
0.0%
☆
P4.30
PULSE maximum input
P4.28~50.00kHz
50.00kHz
☆
P4.31
PULSE maximum input
corresponding setup
-100.00%~100.0%
100.0%
☆
P4.32
PULSE filter time
0.00s~10.00s
0.10s
☆
This group of parameters are used to set relationship between DI5 pulse frequency and it’s
corresponding settings.
Pulse frequency can be only input to the inverter through DI5
channel. This function group’s
applications are similar to curve 1,please refer to the description of curve 1.
P4.33
AI curve selection
1bit
AI1 curve selection
321
☆
Curve1(2 points
,
see P4.13~P4.16)
1
Curve2(2 points
,
see P4.18~P4.21)
2
Curve3(2 points
,
see P4.23~P4.26)
3
Curve4(4 points
,
see A6.00~A6.07)
4
Curve5(4 points
,
see A6.08~A6.15)
5
10bit
AI2 curve selection
Curve1(2 points
,
see P4.13~P4.16)
1
Summary of Contents for HV590 Series